– 33 –
Compressor speed
Maximum speed = WBEMAX
Outdoor fan
See basic
operation
See basic
operation
Med
Set to 7 hours
r
h
5
.
6
r
h
5
.
0
Lo
Indoor fan
Sleep key
Operation lamp
[SLEEP] on the remote
controller is lit
Timer lamp
Hi
Med
Lo
Silent
Sleep
Vertical air
deflector
Facing up
Horizontal
Shut
Notes:
(1)
The sleep operation starts when the sleep key is pressed.
(2)
When the sleep key is set, the maximum compressor speed is limited to WBEMAX, and the indoor fan
is set to “Sleep Silent” (FWSOY).
(3)
If the operation mode is changed during sleep operation, the changed operation mode is set and sleep
control starts.
(4)
The indoor fan speed does not change even when the fan speed mode is changed. (Lo)
(5)
When defrosting is to be set during sleep operation, defrosting is engaged and sleep operation is restored
after defrosting.
(6)
When operation is stopped during sleep operation, the set temperature when stopped, as well as the time,
continue to be counted.
(7)
If the set time is changed during sleep operation, all data including set temperature, time, etc. is cleared
and restarted.
(8)
If sleep operation is cancelled by the cancel key or sleep key, all data is cleared.
(9)
There is no preset temperature shift due to time elapse.
Heating Sleep Operation
1 min
WMIN
DFMAX
Compressor speed
TDF
411
TDF
412
TDF
413 TDF421
WMAX
TDF 431
STARCPL
STARCPL
4000min
-1
4000min
-1
TDF
422
Notes:
(1)
The defrosting inhibit period is set as shown in the diagram below. When defrosting has
finished once, the inhibit period is newly set, based on the outdoor temperature when the
compressor was started. During this period, the defrost signal is not accepted.
(2)
If the difference between the room and outdoor temperatures is large when defrosting is
finished, the maximum compressor speed (WMAX) or (WMAX2) can be continued for 120
minutes maximum.
(3)
The defrosting period is 20 minutes maximum.
(4)
When operation is stopped during defrosting, it is switched to auto refresh defrosting.
(5)
Auto refresh defrosting cannot be engaged within 15 minutes after operation is started or
defrosting is finished.
Reversing Valve Defrosting
Setting Defrosting Inhibit Period
DEFTIM_OTP5
DEFTIM_OTP0
DEFTIM_OTP10
Time
Outdoor temperature
– 1 0
±Û
C
0
Û&
Notes:
(1)
The first inhibit time after operation start is set to DEFTIM_FST.
(2)
From the second time onwards, the inhibit time is set according to the time required for
defrosting.
Reverse cycle operation time
[DEFCOL] : DEFTIM_COL is set.
Reverse cycle operation time < [DEFCOL] : The time corresponding to outdoor tempera-
ture is set.
?