ELECTRICAL WIRING
3
/
3
ENG
L
IS
H
3.
ELECTRICAL WIRING
3.1.
ELECTRICAL WIRING
Up to 8 Central Stations can be connected to the H-LINK.
3.2.
SETTING OF DIP SWITCH
Set the DSW1 as shown below.
Address setting is required when the central
station (Max. 8 units) is connected on H-LINK.
(The setting of dip switches is all OFF before
shipping.)
DSW1 (Address Setting)
Address 1
Address 2
Address 3
Address 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Address 5
Address 6
Address 7
Address 8
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
Divide the power line for the central station from
the main power line by a pull box as shown in
the lfigure.
CAUTION:
-
Check to ensure that the wiring is correct.
Incorrect wiring may cause malfunction of
the central station.
-
Turn OFF the power supply of the air
conditioner and the central station when
performing the wiring work.
-
If the wiring work is performed while the
power supply of the central station is
being supplied, it may cause malfunction
of the central station.
-
DO NOT run all the transmission cable for
the central station along the power line
and other transmission cables, or
malfunction may occur due to the noise,
etc. If the transmission cable for the
central station is required to be run along
the power line and other transmission
cables, separate the cable more than
15cm away from other cables, or run the
cable through a metal tube and earth the
tube.
-
In case of applying high voltage to the
TB2, the fuse on the PCB is blown out.
In such a case, firstly correct the wiring to
TB1, and then set No.2 pin ON.
Remote Control
Switch
Outdoor
Unit
Twist Pair Cable
with shield 0,75mm
2
To be connected to
the terminal board
and
of indoor
unit or outdoor unit
Central Station
Terminal
Board
TB1
Power Supply
(AC 220V or
240V)
To TB2 of
Central Station
H-LINK
Indoor Unit
FG
Terminal
Board
TB2
Pull Box
Indoor Unit
Central Station
To Outdoor Unit or Breaker
220V or 240V
ON
OFF
1 2
DSW3
(Fuse Recover)
Содержание PSC-5S
Страница 2: ......
Страница 4: ...120 mm 120 mm ...