Hitachi NE-S1 series Скачать руководство пользователя страница 14

Chapter 4 

– Further Notes

 

4-1 

Chapter 4 

– Further Notes 

Influence of ground fault monitoring devices 

 

In  the  line  filter,  capacitors  are  placed  between  the  phases  and  ground,  which  can  cause  larger 
charge currents to flow to ground when the filter is first switched on. The amount of this flow has 
already  been  minimized  by  constructional  circuit  details.  Nevertheless,  ground  fault  monitoring 
devices possibly present may be triggered. Ground currents with high-frequency components and 
DC  components  may  also  flow  under  normal  operating  conditions.  If  faults  occur,  large  DC-
carrying ground currents may  flow,  possibly  preventing  the  ground  fault  monitoring  device  from 
responding. For this reason, the use of ground fault monitoring devices is not recommended. 

But  should  they  be  prescribed  in  certain  applications  for  safety  reasons,  you  should  choose 
monitoring devices which are suited for DC, AC and HF ground currents. In addition, you should 
ensure that their responsiveness and time characteristics are adjustable, so that a disturbance is not 
immediately caused the first time the frequency inverter is switched on. 

 

Components susceptible to interference 

 

The  following  components  must  be  classified  as  particularly  susceptible  to  interference  from 
electromagnetic fields. Special attention should therefore be paid to them during installation

 

Sensors with analog output voltages (< 1 volt) 

 

Load cells 

 

Tractive force meters 

 

Torque measuring hubs 

 

Resistance thermometer PT100 

 

Thermoelements 

 

Anemometers 

 

Piezoelectric sensors 

 

AM radios (only long and medium wave) 

 

Video cameras and TV sets 

 

Office PCs 

 

Capacitive proximity switches and filling level sensors 

 

Inductive proximity switches and metal detectors 

 

Ripple control transmitters, baby talkers, etc., i.e. all communication devices which use low-
voltage systems as transmission medium 

 

Devices which do not comply with the pertinent EMC requirements 

 

Содержание NE-S1 series

Страница 1: ...Electromagnetically Compatible Installation Guide Book Inverter Series NE S1 Hitachi Europe GmbH ...

Страница 2: ...ING RADIATED INTERFERENCE 2 5 USING EMC COMPLIANT CABLES 2 6 INSTALLING THE MOTOR CABLE 2 7 INSTALLING CONTROL AND SIGNAL LINES 2 7 SHIELDING AND GROUNDING FOR INSTALLATION IN SWITCH CABINETS 2 8 CHAPTER 3 INFLUENCE OF THE MOTOR CABLE LENGTH 3 1 CHAPTER 4 FURTHER NOTES 4 1 INFLUENCE OF GROUND FAULT MONITORING DEVICES 4 1 COMPONENTS SUSCEPTIBLE TO INTERFERENCE 4 1 CHAPTER 5 TECHNICAL SPECIFICATIONS...

Страница 3: ...ls etc Ignore this and you may get an electric shock WARNING The protective conductor connection between filter and drive must be designed as a solid and permanent installation Plug in connections are not permissible WARNING The use of ground fault monitoring devices is not recommended Should they be compulsory in certain applications for safety reasons you should choose monitoring devices which a...

Страница 4: ... drives very rapidly switch large currents and voltages to optimally supply connected electric motors They are thus major sources of interference generating both line conducted and radiated interference The additional use of line filters also called interference suppression filters and installation in a metal housing or a switch cabinet further improve the existing interference immunity For the be...

Страница 5: ...t in the so called footprint style are fitted behind the respective frequency inverter and thus require no additional space for installation These filters are intended for installation in switch cabinets as standard Vertical mounting next to the frequency inverter is also possible Note All filters are designed for 50 60Hz Frequency Inverter Line Power spcification Line Filter NES1 002 004SBE 1 200...

Страница 6: ...requency inverter or solely via cable shield is not permitted as protective conductor connection The filter must be solidly and permanently connected with the ground potential so as to preclude the danger of electric shock upon touching the filter if a fault occurs You can achieve this by connecting it with a grounding conductor of at least 10mm2 connecting a second grounding conductor connected w...

Страница 7: ... EN61800 3 Cable length Inverter carrier frequency Frequency inverter Category C1 1 25m Max 10kHz NES1 015 022HBE Category C2 50m Max 10kHz 1 The inverter needs to be installed in a metal cabinet to meet category C1 Otherwise category C2 Filter FPF 9340 10 SW Switch position 1 High leakage current EN61800 3 Cable length Inverter carrier frequency Frequency inverter Category C2 50m Max 10kHz NES1 0...

Страница 8: ...rference field emitted by the frequency inverter falls sharply with increasing distance Please note that the emitted interference field frequency range 30 MHz 1 GHz of a drive drive system is measured at a distance of 10 m in accordance with EN61800 3 Every device placed closer than 10 m to a source of interference will thus be impacted by appreciably higher interference amplitudes For this reason...

Страница 9: ...should be preferred when shielding is to be implemented The contact or transition resistance between the individual stranded conductors of the shielding The performance of the shielding improves if this resistance is kept as low as possible The following diagram shows the transfer impedance for various cable types By comparing the cables individual design the shielding effectiveness can be estimat...

Страница 10: ...in the cable If the use of reactors contactors terminals or safety switches in the motor output is necessary i e if the shield must be interrupted then the unshielded section should be kept as small as possible It is better to install the reactor contactor terminal or safety switch in a metal housing with as much HF damping as possible The shield connection to the metal housing should again be mad...

Страница 11: ...andard EN60204 1 Electrical Equipment of Industrial Machinery You get optimum EMC only if you properly arrange and mount the Hitachi frequency inverter the appropriate line filter and the other equipment which might be necessary on a metal mounting plate in accordance with the following mounting instructions The following figure shows a Hitachi inverter using a foot print filter NE S1 ...

Страница 12: ...patible installation of drives and drive systems 2 9 The following figure shows the required EMC compliant connection to the motor good HF connection between heat sink and motor housing required EMC cable connection metall box U V W PE ...

Страница 13: ...riggering of a ground fault monitoring device that may be present Long motor cables lead to thermal overload of the line filter due to the higher line conducted interference If a motor choke of appropriate size is used you have the following advantages It can counteract unwanted shut off due to overload described above The thermal load on the EMC line filter is reduced In multiple motor applicatio...

Страница 14: ... monitoring devices which are suited for DC AC and HF ground currents In addition you should ensure that their responsiveness and time characteristics are adjustable so that a disturbance is not immediately caused the first time the frequency inverter is switched on Components susceptible to interference The following components must be classified as particularly susceptible to interference from e...

Страница 15: ...Output cable 2x2 5 mm 2x2 5 mm 3x4 mm 3x2 5 mm 3x2 5 mm Weight in kg approx 0 5 1 0 0 9 0 7 1 2 Heat dissipation in W approx 2 5 10 4 7 1 Worst case states the leakage current for three phase filters in the worst of cases That means one phase is live and two phases of the feed line lead in are interrupted These maximum values are based on an operating voltage of 460 V ph ph 2 The normal leakage cu...

Страница 16: ...Chapter Technical specifications and dimensions of NE S1 filter 5 2 FPF 9120 10 SW FPF 9120 14 SW FPF 9120 24 SW ...

Страница 17: ...Chapter Technical specifications and dimensions of NE S1 filter 5 3 FPF 9340 05 SW FPF 9340 10 SW ...

Страница 18: ...the interface point between the user s supply and the public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a short circuit power Ssc greater than or equal to the value mentioned in the table below Inverter model AC DC reactor Norm Ssc Rsce ...

Отзывы: