Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–44
Analog Input Disconnect Detect
This feature is useful when the inverter receives a speed reference from an external
device. Upon input signal loss at either the [O] or [OI] terminal, the inverter normally
just decelerates the motor to a stop. However, the inverter can use the intelligent output
terminal [Dc] to signal other machinery that a signal loss has occurred.
Voltage signal loss at [O] terminal - Parameter B082 is the Start Frequency Adjust-
ment. It sets the beginning (minimum) output frequency when the speed reference
source is greater than zero. If the analog input at terminal [O] is less than the Start
Frequency, the inverter turns ON the [Dc] output to indicate a signal loss condition.
Current signal loss at [OI] terminal - The [OI] terminal accepts a 4mA to 20mA
signal, with 4mA representing the beginning of the input range. If the input current falls
below 4mA, the inverter applies a threshold to detect signal loss.
Note that a signal loss is not an inverter trip event. When the analog input value is again
above the B082 value, the [Dc] output turns OFF. There is no error condition to clear.
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
06
Dc
Analog Input
Disconnect Detect
ON
when the [O] input value < B082 Start
Frequency Adjustment (signal loss detected), or
when the [OI input current is less than 4mA
OFF
when no signal loss is detected
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
A001=01, B082
Notes:
•
The [Dc] output can indicate an analog signal
disconnect when the inverter is in Stop Mode, as
well as Run Mode.
•
The example circuit for terminal [12] drives a relay
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from
damaging the inverter’s output transistor.
RY
+
–
Example (requires output configuration—
see page
Inverter output
terminal circuit
Dc
Example for terminals [AL0], [AL1], [AL2]
(requires output configuration—
see pages
AL0
AL2
AL1
Inverter logic
circuit board
See I/O specs
on page
Dc
Load
Power
supply
12 11
CM2
Содержание L200 Series
Страница 2: ......
Страница 40: ......
Страница 186: ......
Страница 187: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 192: ......
Страница 209: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 256: ......
Страница 257: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 268: ......
Страница 269: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 D ...
Страница 273: ...L200 Inverter Appendix D D 5 L1 L2 L3 PE L200 inverter with book type filter M 3 ...