L100 Inverter
T
roub
leshooting
and Maintenance
6–7
Trip History and Inverter Status
We recommend that you first find the cause of the fault before clearing it. When a fault
occurs, the inverter stores important performance data at the moment of the fault. To
access the data, use the monitor functions (D_xx) and select D_08 for details about the
present fault (E
n
), or the error code for the past two trip events (E
n-1
and E
n-2
) using the
D_09 Trip History function.
The following Monitor Menu map shows how to access the error codes. When fault(s)
exist, you can review their details by first selecting the proper function: D_08 displays
current trip data, and D_09 displays trip history.
2
1
Error Code
Previous
error #1
FUNC.
FUNC.
FUNC.
FUNC.
FUNC.
FUNC.
Output frequency
at trip point
Motor current
at trip point
DC bus voltage
at trip point
No error
Yes
No
FUNC.
Yes
No
Yes
No
Previous
error #2
FUNC.
No
history
No
history
FUNC.
FUNC.
FUNC.
2
1
2
2
d
0 8
E 0 9
d
0 1
d
0 9
1 0.0
0.25
18 9.8
_ _ _
E 0 3
_ _ _
_ _ _
E 0 5
Monitor Menu
Current Trip
Conditions
Trip History
Error
(n-1)
exists?
Error
exists?
Error
(n-2)
exists?
Содержание L100 Series
Страница 145: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 5 5 ...
Страница 168: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Страница 176: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 B ...
Страница 183: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 6 C ...
Страница 186: ...CE EMC Installation Guidelines Appendix C C 4 L1 L2 L3 PE M 3 L100 inverter with footprint type filter ...
Страница 187: ...L100 Inverter Appendix C C 5 L1 L2 L3 PE L100 inverter with book type filter M 3 ...