H E A T   P U M P   W A T E R   H E A T E R   C O M P R E S S O R   C R I T E R I A  

PAGE:12/31 

(6)The compressor can

t be used in the place with corrosive atmosphere such as hot

spring and chemical warehouse. It should not be the structure often splash water on the

surface of the compressor forcibly. 

(7) The trouble of cross valve, electromagnetic valve, defroster, refrigerant controller,

fan motor used in refrigerating system may cause compressor accident .So their reliability 

should be ensured completely. Moreover, the way of design, manufacture, application of 

refrigeration cycle with less-leak should be adopted. 

(8)The main electric circuit should be equipped with fuse or breaker.   

(9)Refrigerant should be charged from the end of condenser of refrigerating systems. 

e e  

Charge refrigerant to the compressor directly. 

The refrigerant should always be charged in liquid state. When the refrigerant is 

charged in gas state. The percent component will possibly be changed.   

(10) Temperatures within systems during stable compressor operation should not be less  

than -35℃ to prevent wax precipitation from the oil. 

(11) The units of refrigerating system should be connected to earth. 

12)Compressor mounting

 

Rubber grommets are designed soft to provide the noise isolation and to lessen vibration

Energy transmission. Stud bolt should be designed to provide sufficient clearance for 

noise andvibration isolation and to prevent compressor from coming off its mount. 

橡胶避振脚是采用防止由于噪音引起的振动及振动能量吸收原理设计的。所设计的固定杆应提供

足够的间隙用于噪音及振动隔离,并且防止压缩机从避振脚上滑落。 

(13)   There should be adequate clearance between the under-surface of Push-Nut and the  

upper surface of rubber grommets.  

Содержание Highly WHP13300PSD

Страница 1: ...ssors Spezifikation Installation Manual RIES GmbH Rudolf Diesel Str 10 D 64569 Nauheim GERMANY Phone 49 6152 9741 0 Fax 49 6152 9741 21 Email info ries gmbh de Website www ries gmbh de R 290 54 8 cm3 rev 900 6600 min 1 WHP13300PSDPC8FQ DC BLDC ...

Страница 2: ...HE MODEL 3 THE PARAMETER OF MOTOR 4 CHARACTERISTICS 5 PARTS AND DRAWING LIST 5 15 HEAT PUMP Compressor CRITERIA 16 CHECK UPON DELIVERY 1 BASIS FOR CHECKING UPON DELIVERY 2 RULE FOR CHECKING UPON DELIVERY 17 26 DRAWINGS 0 27 30 ATTACHED PAGE 31 SPECIFICATION REVISION RECORD ...

Страница 3: ...ower source input to inverter Rated voltage Rated frequency Phase 380V 50Hz 3ФOR 220V 50HZ 1Ф 2 3 Output 2630W 3600 min 1 2 4 Application Heat pump water heater 2 5 Performance Item Rated Condition Rotational speed 3600 min 1 Nominal Heating Capacity 13300W 5 Motor input 2860W 5 Current 11 5A 5 COP see 4 65 5 Test Conditions Evaporating temp 7 2 Condensing temp 54 4 Liquid temp entering expansion ...

Страница 4: ...erant c h a r g e Below 1500g 2 11 Hermetic Terminal Conventinal Type 2 12 Space volume of inner case 1500cm 3 2 13 Compressor weight 18 9kg incl Oil 2 14 Motor Type Insulation class Direct current brushless motor E class 2 15 Compressor natural frequencies 19 9Hz 21 7Hz 24 5Hz 3Hz should be avoided or pass within ten seconds are compressor natural frequencies and they can be changed when connecti...

Страница 5: ...tance Ld mH Sheet 2 3 5 Inductance Lq mH Sheet 2 3 6 Stator coil resistance 20 Ω 0 502 20 line to line 3 7 Voltage Constant Vrms krpm 43 10V krpm line to line 3 8 Torque Constant N m Ams 0 69 Torque Current 力矩 电流 3 9 Inertia Kg m2 0 000666 3 10 Flux Φa Wb 0 1702 φ Per Phase Peak 3 2 0 2 f E π φ 一相 peak 值 3 2 0 2 f E π 3 11 Magnet Material NdFeB Current 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 q 5 44 5 ...

Страница 6: ...ING NO REMARKS Compressor 1 4CYCH0638 Dimensioned sketch Mounting Parts Rubber grommet Bolt Nut 3 4CYC00643 4CYC00700 M8 Electrical Parts Thermostat Terminal cover Gasket Nut Rubber washer Sleeve 1 1 1 1 1 1 4CYC01403 4CYC00988 4CYC01047 3CYC00004 4CYC00174 4CYC01042 4CYC01272 1 2 3 Lead routing Pressure guarantee Chart Pressure Guarantee Range Chart Notes for rotational speed change Performance c...

Страница 7: ...ect current motor will demagnetize 3 Operating voltage range The compressor should be operated in the range of rated voltage 10 under standard condition and overload condition of rated frequency applied voltage to inverter It must be satisfied with item 5 6 7 4 Operating temperatures and pressures The operating temperatures and pressures of a compressor should be within the range shown in the tabl...

Страница 8: ...25 Compressor suction side can handle the same maximum pressure as discharge side without damage when compressor is not running Compressor case bottom temp 99 or below and 6 higher than condensing temperature the time compressor case bottom temp 6 below the condensing temperature should be less than 5 minutes each time Requirement for high pressure ratio condition can be seen on page 28 Motor wind...

Страница 9: ...tion 7 Pressure difference between suction and discharge 吸气 排气压力差 In all allowable rotational speed range the difference of pressure should be more than 0 39MPa 4kgf cm 2 But if there is no problem of noise when assembled in air conditioner it can also below this value the requirement can be seen on page 28 8 Discharge pipe temperature Discharge pipe temperature is measured at a distance 300mm fro...

Страница 10: ...e minimum level Stopping time should be more than 3 minutes to make sure the suction pressure and discharge pressure is balance 12 Rate of rotational speed change The rate of compressor rotational speed acceleration should be less than 133min 1 s as the compressor speed is below 5400rpm while less than 60min 1 s as the compressor speed is higher than 5400rpm However when rotational speed is reduce...

Страница 11: ...s washing fluid used at machining heat exchanger and tubes 15 Compressor vacuum operation Compressor should never be operated while under vacuum Otherwise internal arcing can cause damaging parts 16 The compressor should be operated for more than 20 seconds within 15 minutes after charging refrigerant into the system so proper lubrication results 17 Liquid refrigerant return limitations 有关液体制冷剂回流的...

Страница 12: ...ving equipment such as automobiles trains ships etc 20 Installation The rotational axis of compressor should be kept vertical during operation But in actual application the axis incline must be within 5 at all directions during operation 21 Pipe vibration The displacement of the pipes which connect from the compressor to other parts of the refrigerate or systems should be less than 0 8mm 1 32 when...

Страница 13: ...uld not apply partial force on projection parts such as pipe hermetic terminals foot during carrying and processing 2 The compressor should not be operated to form a vacuum and to absorb air The compressor only can run in one direction which according to lead routing wiring diagram Never reversion otherwise thecompressor will be in trouble 3 The compressor should not be left opened in the atmosphe...

Страница 14: ...r of refrigerating systems e e Charge refrigerant to the compressor directly The refrigerant should always be charged in liquid state When the refrigerant is charged in gas state The percent component will possibly be changed 10 Temperatures within systems during stable compressor operation should not be less than 35 to prevent wax precipitation from the oil 11 The units of refrigerating system sh...

Страница 15: ...sor to reach the temperature higher than 10 with heater if the ambient temperature is below 10 19 Set a thermistor on the case cover of compressor to prevent from accident of leakage of refrigerant The thermistor can stop the operation of compressor when compressor in abnormal temperature The lead wires of thermostat is enveloped with tube as same as that of the terminals to avoid directcontact wi...

Страница 16: ...r 23 Be careful of avoiding oxide scale while soldering during assembly of refrigerating system for example flow or fulfill dry nitrogen 24 The quantity and kind of contamination the process materials in the cycle should be grasped and managed Carry on reliability test that input contamination a lot than anticipated contamination quantity 25 To avoid water and impurity into he refrigeration system...

Страница 17: ... 31 27 The fuse or and breaker should be equipped in the main circuit 28 The thickness of the refrigerating system using tube the tube thickness as followed External diameter mm 6 35 6 35 11 0 11 0 13 0 13 0 15 0 15 0 19 0 Thickness 0 5 0 5 0 6 0 6 0 8 ...

Страница 18: ...lar electrical appliances General requirements and GB 4706 17 Safety of household and similar electrical appliances Particular requirements for motor compressor 2 Rule for Checking upon Delivery If come across any quality problem please notify the company in written form within 30 days after the arrival of the cargo the company shall exchange exactly the number of the products otherwise they shall...

Страница 19: ...17 31 ...

Страница 20: ...18 31 ...

Страница 21: ... 19 31 ...

Страница 22: ...20 31 ...

Страница 23: ...21 31 ...

Страница 24: ...22 31 ...

Страница 25: ...23 31 ...

Страница 26: ...24 31 ...

Страница 27: ...25 31 ...

Страница 28: ...26 31 ...

Страница 29: ...0 1 WHP13300PSDP Pd Pd PRESSURE MPa A 1000 2000 3000 4000 5000 6000 7000 8000 0 5 1 5 2 5 a b d c 1 Compressor running speed range Min 900min 1 Max 6600min 1 Rotational speed Pd limit 900 1 71 2000 3 13 5400 3 13 6600 2 34 27 31 ...

Страница 30: ...mation of operating conditions the stage when pressure or temperature changing rapidly 28 31 Condition 1 Condition 2 Condition 3 Condit ion 4 Condit ion 5 Condit ion 6 Range of the conditions Ps Psmax 0 137 Ps 0 168MPa A Pressure ratio 8 Pressure ratio 1 5 Pressure difference 0 39 MPa The oil Temperatur SH 6 Operations requirement 1 Frequecy 70Hz 2 Ps 1 3MPa A 3 Pd Pdmax 1 Rotational speed N 6600r...

Страница 31: ...29 31 ...

Страница 32: ...gewünschten Drehzahl From starting to normal running Rotation speed Drehzahl 1 min 2 Niedrige Drehzahl und unregelmäßiger Betrieb Low speed un continuosly running Drehzahl Rotation speed 1 Os I I 2200 min 1 Min Drehzahl Speed 1 min 1 1 3 min 3 Abtauung Defrost mode unter Verwendung eines 4 Wege Ventiles b y using 4 way valve Drehzahl Rotation speed Max Drehzahl Max speed Max Drehzahl Speed 1 2400m...

Страница 33: ...Specification Revision Record No Date Page in Spec Revision Reason Conclusion Date A B C D E F G H J K L M N P Q R S U V 31 31 ...