4 Troubleshooting
Troubleshooting by alarm code
SMGB0120 rev.0 - 11/2017
97
4
4.8
Troubleshooting by alarm code
Alarm code
C1-H1
High Pressure Switch
Alarm stop reason
Discharge pressure (Pd) increases up to 2.02MPa, activating high pressure switch (63H).
PCB monitoring position
PCBd (I/O PCB) PCN204 (High pressure interruption device (63H))
Check of PCBd (I/O PCB)
Press the reset button of
high pressure switch
Check of high pressure
switch (63H) (Internal
disconnection)
Check of wiring
(disconnection)
Excessive refrigerant load
Insufficient volume of water
Reverse rotation of pump
Air mixture
Clogging of water strainer
Malfunction of expansion valve
Excessive refrigerant load
Opening of liquid stop valve
forgotten
Formation of lime deposit in water
side heat exchanger
In case of cooling operation
I/O PCB is normal
Check of PCBd (I/O PCB)
Yes
No
Yes
No
Revision of connections
The connection and
insertion of connector
PCN204 to PCBd (I/O
PCB) are correct
Yes
No
Yes
No
Yes
No
In case of heating operation
Remove the wires
inserted in PCN204
on PCBd (I/O PCB) and
check power conduction.
Is there power
conduction?
High pressure
switch (63H) is
activated.
Operation control results
in immediate alarm
High pressure
switch (63H) is being
reset