214
(8-7/16)
20
(1-13/16
)
39 (1-9/16)
40
(1-9/16)
54
(2-1/8)
151
(5-15/16)
63(2-1/2)
Service Cover for
Electronic Expansion Valve
Low Pressure
Gas Pipe Connection
(
φ
19.05(3/4) Flare Nut)
Gas Pipe Connection
(
φ
A Flare Nut)
High/Low Pressure
Gas Pipe Connection
(
φ
15.88(5/8) Flare Nut)
Service Cover for
Electrical Box
Electrical Box
(Available for
Both Sides)
Outdoor Unit Connecting Side
38
(1-1/2)
301(11-7/8)
376(14-13/16)
Unit: mm(inch)
82
(3-1/4)
89
(3-1/2)
301(11-7/8)
B
180
(7-1/16)
191(7-1/2)
111
(4-3/8)
25(1)
Indoor Unit Connecting Side
38
(1-1/2)
5.2
Refrigerant
Piping
Work
Provide
the
refrigerant
pipe
in
the
field
.
Make
sure
that
the
refrigerant
pipe
is
connected
to
the
same
refrigerant
cycle
unit.
(1)
Position
of
Piping
Connection
Dimension
Model
A
B
HCHS-N06X
15.88(5/8)
89(3-1/2)
HCHS-N10X
19.05(3/4)
96(3-3/4)
(2)
Selecting
Piping
Size
(a)
Select
the
size
for
the
high/low
pressure
gas
pipe,
low
pressure
gas
pipe
and
gas
pipe
according
to
the
table
5.1.
The
size
depends
on
the
indoor
unit
total
capacity
connected
downstream
of
the
Switch Box
.
(b) In case that the piping size from Table 5.1 and the piping connection size for
Switch Box
from Table
5.2 are different, use an accessory pipe according to the item 5.2(3).
(c) As for the
BRANCH PIPE
branch or header branch, refer to Technical Catalog for Outdoor Unit.
Table
5.1
Connected
Indoor
Unit
Capacity
and
Piping
Size
Model
Connected
Indoor
Unit
Capacity
Low
Pressure
Gas
Pipe
High/Low
Pressure
Gas
Pipe
Gas
Pipe
(HP)
(mm)
(mm)
(mm)
HCHS-N06X
1.5HP
or
less
ɸ15.88
ɸ12.7
ɸ12.7
T
1.6
to
4.0
ɸ15.88
ɸ12.7
ɸ15.88
4.1
to
6.0
ɸ19.05
ɸ15.88
ɸ15.88
HCHS-N10X
6.1
to
8.0
ɸ19.05
ɸ15.88
ɸ19.05
8.1
to
10.0
ɸ22.2
ɸ19.05
ɸ22.2
T
: In case that a branch is located downstream of the
Switch Box
and also the connected indoor unit capacity is
1.5HP
or
less,
use
ɸ15.88
for
the
gas
pipe.
Table 5.2 Piping Connection Size for
Switch Box
Model
Low
Pressure
Gas
Pipe
High/Low
Pressure
Gas
Pipe
Gas
Pipe
(mm)
(mm)
(mm)
HCHS-N06X
ɸ19.05
ɸ15.88
ɸ15.88
HCHS-N10X
ɸ19.05
ɸ15.88
ɸ19.05
Indoor
Unit
Indoor
Unit
Upstream
BRANCH PIPE
Downstream
Low Pressure
Gas Pipe
Switch Box
High/Low Pressure
Gas Pipe
Gas Pipe
11