![Hirschmann SPIDER Premium Line Скачать руководство пользователя страница 42](http://html1.mh-extra.com/html/hirschmann/spider-premium-line/spider-premium-line_user-manual_2138065042.webp)
42
Installation SPIDER-PL
Re
lease
03
08/2
016
Electromagnetic field
EN 61000-4-3
10 V/m
10 V/m
20 V/m
10 V/m
IEEE 1613
—
—
—
35 V/m
Fast transients (burst)
EN 61000-4-4
IEEE C37.90.1
Supply connection
± 2 kV
± 2 kV
± 2 kV
± 4 kV
EN 61000-4-4
IEEE C37.90.1
Data line
± 4 kV
± 4 kV
± 2 kV
± 4 kV
Voltage surges - DC supply connection
EN 61000-4-5
line/ground
± 2 kV
± 2 kV
± 2 kV
± 2 kV
IEEE 1613
line/ground
—
—
—
± 5 kV
EN 61000-4-5
line/line
± 1 kV
± 1 kV
± 1 kV
± 1 kV
Voltage surges - data line
EN 61000-4-5
line/ground
± 1 kV
± 1 kV
± 2 kV
± 2 kV
Conducted disturbances
EN 61000-4-6
150 kHz ... 80 MHz
10 V
10 V
10 V
10 V
Damped vibration – DC supply connection
EN 61000-4-12
IEEE C37.90.1
line/ground
—
—
—
2.5 kV
EN 61000-4-12
IEEE C37.90.1
line/line
—
—
—
1 kV
Damped oscillation - data line
EN 61000-4-12
IEEE C37.90.1
line/ground
—
—
—
2.5 kV
EN 61000-4-12
line/line
—
—
—
± 1 kV
Pulse magnetic fields
EN 61000-4-9
—
—
300 A/m
—
EMC interference immunity
Standard
applications
a
Marine
applications
b
Railway
applications
(trackside)
c
Sub-station
applications
d