2
Power supply quality parameters are necessary in order to investigate and analyze the phenome-
non of power supply problems
*1
. By measuring these parameters, it is possible to assess power
supply quality. In order to allow the PQ3198 to detect abnormal values and abnormal waveforms,
you set thresholds
*2
. When these thresholds are exceeded, events are generated.
*1: Meaning issues caused by a reduction in power supply quality, resulting in the following substation
issues and electronically controlled device malfunctions: lighting flicker, frequent burning out of incan-
descent light bulbs, malfunctioning office equipment, occasional abnormal machine operation, over-
heating of reactor-equipped capacitor equipment, and occasional malfunctioning of overload,
negative-phase, and open-phase relays.
*2: Thresholds are set based on an estimation of abnormal values, so events do not necessarily indicate
a problem.
Appendix 2 Explanation of Power Supply Quality
Parameters and Events
Principal
parameters
indicating
power quality
Waveform
Phenomenon
Primary issues
PQ3198 events and
measurements
Frequency
fluctuations
Occurs due to line
separation caused by
changes in the supply/
demand balance of
active power, the shut-
down of a high-capac-
ity generator, or circuit
issues.
Changes in the speed
of synchronized
motors may cause
product defects.
Events are detected
using frequency 200 ms
(Freq) and frequency
cycle (Freq_wav). Mea-
surement items include
IEC61000-4-30 10-sec-
ond average frequency
and 10-second fre-
quency (Freq10s).
Transient
overvoltage
(impulse)
Occurs due to phe-
nomena such as light-
ning, breaker point
damage, or closure on
the circuit breaker or
relay.
Often occurs when
there is a radical
change in voltage or
when the peak volt-
age is high.
Close to the source of
the break, the device's
power is damaged
because of exception-
ally high voltages and
this may cause the
device to reset.
Events involving tran-
sients of 5 kHz or
more are detected
using transient over-
voltage. They can also
be detected as voltage
waveform distortions
using voltage wave-
form peak and voltage
waveform comparison
functionality.
Voltage dip
(SAG)
Most dips are caused
by natural phenom-
ena such as lighting.
When an equipment
fault is detected and
taken offline due to the
occurrence of a power
system ground fault or
short-circuit, a large
inrush current caused
by a motor startup or
other load can occur,
causing a temporary
voltage dip.
Dips in the supply volt-
age can cause equip-
ment to stop operating
or be reset, discharge
lamps to turn off, elec-
tric motors to increase
or decrease in speed
or stop, or synchro-
nized motors and gen-
erators to lose
synchronization.
Events are detected
using dips.
HIOKI PQ3198A961-03
Содержание PQ3198
Страница 2: ...HIOKI PQ3198A961 03...
Страница 6: ...Contents iv HIOKI PQ3198A961 03...
Страница 20: ...Usage Notes 14 HIOKI PQ3198A961 03...
Страница 44: ...2 3 Display Items and Screen Types 38 HIOKI PQ3198A961 03...
Страница 58: ...3 8 Turning the Power On and Off Setting the Default Language 52 HIOKI PQ3198A961 03...
Страница 102: ...5 8 Factory Settings 96 HIOKI PQ3198A961 03...
Страница 116: ...6 4 Displaying Harmonics 110 Holding the display Hold Measured values and waveforms will be held HIOKI PQ3198A961 03...
Страница 198: ...12 4 Downloading Recorded Data to Computer 192 HIOKI PQ3198A961 03...
Страница 264: ...14 4 Disposing of the Instrument 258 HIOKI PQ3198A961 03...
Страница 296: ...A32 HIOKI PQ3198A961 03...
Страница 299: ...Index Index 3 Index Wiring 73 Z Zero adjustment 53 Zero phase A28 HIOKI PQ3198A961 03...
Страница 300: ...Index Index 4 HIOKI PQ3198A961 03...
Страница 301: ...HIOKI PQ3198A961 03...
Страница 302: ...HIOKI PQ3198A961 03...
Страница 303: ...HIOKI PQ3198A961 03...
Страница 304: ...www hioki com HIOKI PQ3198A961 03...