Internal
5.1、
Public parameters
No
Option
Definition
Default
值
Adjustment Range
1.1
SYSTEM TIME
\
\
Real time
1.2
BACKLIGHT
Min
Active
Active /1-30 Min
1.3
BRIGHTNESS
REGULATION
Standby / work
15/30
0-100/10-100
1.4
PERMISSIONS
VALID TIME
Min
Active
Active /1-30 Min
1.5
USER
PASSWORD
\
1000
0000-9999
5.2、
System parameters
No
Option
Definition
Default
Adjustment Range
2.1
NETWORK
Network Type
4NBL
4NBL
2.2
NOM.VOLT.
P-P Voltage
400
50-690V
2.3
APP
M-M:Mains to Mains Supply
M-M
M-M
2.4
RETURNS
Inhibit the automatic
retransfer
Automatc
retransfer
to the
priority
source
Automatic retransfer
to the priority source /
Don’t automatic
retransfer to the
priority source
2.5
NOM.FREQ.
Nominal network frequency
50 Hz
50/60Hz
2.6
POT PH.
Select and verify Phase
Sequence
OFF
L1L2L3/ L3L2L1/ OFF
2.7
1RT
Source I Return Timer
3S
0-99S
2.8
1FT
Source I Failure Timer
3S
0-99S
2.9
2RT
Source II Return Timer
3S
0-99S
2.10
2FT
Source II Failure Timer
3S
0-99S
2.11
UND.U
Under-voltage threshold
85%
70-95%
2.12
UND.U.HYS
Under-voltage hysteresis
95%
75-100%
2.13
OV.U
Over-voltage threshold
115%
105-130%
2.14
OV.U.HYS
Over-voltage hysteresis
110%
100-125%
2.15
UND.F
Under- Frequency threshold
95%
80-99%
2.16
UND.F.HYS
Under- Frequency hysteresis
97%
88-100%
2.17
OV.F
Over- Frequency threshold
105%
101-120%
2.18
OV.F.HYS
Over- Frequency hysteresis
103%
100-119%