4 Start-up
X-MIO 7/6 01
Page 54 of 72
HI 801 305 E Rev. 5.00
4.5.9
Submodule Status DO 02 [DWORD]
Coding of the
Submodule Status
Coding
Description
0x00000001
Fault in hardware unit (submodule)
0x00000002
Reset of an I/O bus
0x00000004
Faults detected while configuring the hardware
0x00000080
Reset of CS monitoring (Chip Select monitoring)
0x00800000
Voltage monitoring of WD1: voltage error
0x01000000
Voltage monitoring of WD2: voltage error
0x02000000
Voltage monitoring of L1+ HIGH voltage defective
0x04000000
Voltage monitoring of L1+ LOW voltage defective
0x08000000
Voltage monitoring of L2+ HIGH voltage defective
0x10000000
Voltage monitoring of L2+ LOW voltage defective
0x20000000
Error while reading back the relay voltage
0x40000000
Error while reading back the outputs, safety switch triggered
0x80000000
Error while reading back the outputs, watchdog triggered
Table 34: Submodule Status DO 02 [DWORD]
4.5.10
Submodule Status DI 02 [DWORD]
Coding of the
Submodule Status
Coding
Description
0x00000001
Fault in hardware unit (submodule)
0x00000002
Reset of an I/O bus
0x00800000
Module fault reference voltage A
0x01000000
Fault reference voltage A (overvoltage)
0x02000000
Fault reference voltage B (undervoltage)
0x04000000
Module fault reference voltage B
0x08000000
Fault auxiliary voltage
0x10000000
Fault reference voltage A (undervoltage)
0x20000000
Fault reference voltage B (overvoltage)
0x40000000
Fault chip select monitoring A
0x80000000
Fault chip select monitoring B
Table 35: Submodule Status DI 02 [DWORD]