X-CPU 01
4 Start-up
HI 801 009 E Rev. 4.00
Page 41 of 52
Starting up Several Processor Modules
If the supply voltage is connected for a HIMax system containing several processor
modules, the processor modules themselves determine which processor module will start
the first. The system automatically controls the start order.
If the mode switch on the first processor module is in the Run position, the system starts
automatically, provided that Autostart was previously configured. All remaining processor
modules follow and start system operation, unless their switch position is set to is Init.
If the mode switch of the first processor module is in the Stop position, this processor
module adopts the STOP state and the user program does not start. All remaining
processor modules follow and enter the STOP state, unless their switch position is set to
Init, see Chapter 3.4.18.
The Init switch position does not influence the other processor modules.
i
Before switching on the supply voltage, set the mode switch of all processor modules to the
Run position to ensure that the system can safely start system operation.