System Manual M45
7 Start-Up
HI 800 651 E Rev. 1.01
Page 55 of 80
Switch /
Parameter
Function
Default
value
Setting for
safe operation
Reload Allowed
ON: User program reload is permitted
ON
Application-
specific
OFF: User program reload is not permitted
Local Forcing
Allowed
ON: Forcing permitted at program level
OFF
OFF is
recommended
OFF: Forcing not permitted at program level
Local Force
Timeout Reaction
Behavior of the user program after the forcing time has
expired:
Stop Forcing Only.
Stop Program.
Stop
Forcing
Only.
Application-
specific
Code Generation
Compatibility
SILworX V4 Code generation is compatible with
SILworX V4.
SILworX
V4
SILworX V4
SILworX V3 Not applicable for HIMatrix controllers!
SILworX V2 Code generation is compatible with
SILworX V2. Not applicable/not
recommended for HIMatrix M45 controllers!
Table 30: System Parameters of the User Program
Notes specific to the
Code Generation Compatibility
Parameter
:
In a new project, SILworX selects the latest value for the
Code Generation Compatibility
parameter. This ensures that the current, enhanced features are activated and the latest
hardware and operating system versions are supported. Verify that this setting is in
accordance with the hardware in use. HIMatrix M45 needs the value SILworX V4 for the
parameter
Minimum Configuration Version
.
In a project converted from a previous SILworX version, the value for
Code Generation
Compatibility
remains the value set in the previous version. This ensures that the
configuration CRC resulting from the code generation is the same as in the previous version
and the generated configuration is compatible with the operating systems in the hardware.
For this reason, the value of
Code Generation Compatibility
should not be changed for
converted projects.
If a
Minimum Configuration Version
of
SILworX V4
or higher is set for a resource (see
above), the
Code Generation Compatibility
parameter must be set to
SILworX V4
in every
user program.
7.5.4
Configuration of the Hardware Image
Before configuring the details of inputs, outputs and communication interfaces, create the image
of the M45 hardware used in the SILworX Hardware Editor. The image contains all modules in
the order they are placed on the DIN rail (or should be placed). The image is created
independently of the hardware installation.
The Hardware Editor only represents processor modules, communication modules, and I/O
modules. Additional hardware, as the power module M-PWR 01, cannot be represented.
While planning an M45 resource, it is possible to insert modules between adjacent modules. In
this case, SILworX shifts all modules located to the right of the insertion position, one position
further to the right. If a module is removed, SILworX shifts all modules to its right one position to
the left.
The
Insert Linebreak
function can be used to represent the system bus extension and how the
modules are distributed over multiple rails.
Insert Linebreak
wraps the modules into multiple
rows. The sockets for extending the system bus necessary for the real hardware are not
represented.
7.5.5
Configuring the Inputs and Outputs
In the Hardware Editor, the inputs and outputs are configured by connecting global variables to
the system variables for input and output channels.