4 Start-up 

F3 DIO 20/8 02 

Page 28 of 48 

HI 800 345 E Rev. 2.00 

4.1.4 

Mounting the F3 DIO 20/8 02 in Zone 2 

(EC Directive 94/9/EC, ATEX) 

The remote I/O is suitable for mounting in zone 2. Refer to the corresponding declaration of 
conformity available on the HIMA website. 

When mounting the device, observe the special conditions specified in the following section. 

Specific Conditions X 

1.  Mount the remote I/O in an enclosure that meets the EN 60079-15 requirements and 

achieves a type of protection of at least IP54, in accordance with EN 60529. Provide the 
enclosure with the following label: 
 

Work is only permitted in the de-energized state

 

 
Exception: 
If a potentially explosive atmosphere has been precluded, work can also performed when the 
controller is under voltage. 

2.  The enclosure in use must be able to safely dissipate the generated heat. Depending on the 

output load and supply voltage, the HIMatrix F3 DIO 20/8 02 has a power dissipation ranging 
between 9 W and 25 W. 

3.  Protect the HIMatrix F3 DIO 20/8 02 with a 10 A time-lag fuse. 

The 24 VDC power must come from a power supply unit with safe isolation. Use power 
supply units of type PELV or SELV only. 

4. Applicable standards: 

VDE 0170/0171 Part 16, 

DIN EN 60079-15: 2004-5 

VDE 0165 Part 1,  

 

DIN EN 60079-14: 1998-08 

 
Pay particular attention to the following sections: 

DIN EN 60079-15: 

 

Chapter 5 

Design 

Chapter 6 

Terminals and cabling 

Chapter 7 

Air and creeping distances 

Chapter 14 

Connectors 

DIN EN 60079-14: 

 

Chapter 5.2.3 

Equipment for use in zone 2 

Chapter 9.3 

Cabling for zones 1 and 2 

Chapter 12.2 

Equipment for zones 1 and 2 

 

The remote I/O is additionally equipped with the label represented below: 

 

Figure 8:  Label for Ex Conditions 

 

Содержание HIMatrix F3 DIO 20/8 02

Страница 1: ...HIMatrix Safety Related Controller F3 DIO 20 8 02 Manual HIMA Paul Hildebrandt GmbH Co KG Industrial Automation Rev 2 00 HI 800 345 E...

Страница 2: ...ncluded in the manual Equipment subject to change without notice HIMA also reserves the right to modify the written material without prior notice For further information refer to the HIMA DVD and our...

Страница 3: ...action in the Event of a Fault 12 3 1 1 2 Line Control 12 3 1 2 Safety Related Digital Outputs 13 3 1 2 1 Reaction in the Event of a Fault 14 3 2 Equipment Scope of Delivery 15 3 2 1 IP Address and Sy...

Страница 4: ...2 1 Tab Module 30 4 3 2 2 Tab DI 20 Channels 31 4 3 3 Digital Outputs of F3 DIO 20 8 02 32 4 3 3 1 Tab Module 32 4 3 3 2 Tab DO 8 Channels 33 4 4 Configuration with ELOP II Factory 34 4 4 1 Configuri...

Страница 5: ...on Maintenance Decommissioning Transport Disposal HIMatrix remote I Os are available for the programming tools SILworX and ELOP II Factory Which programming tool can be used depends on the processor o...

Страница 6: ...Help Instructions on how to use SILworX ELOP II Factory Online Help Instructions on how to use ELOP II Factory Ethernet IP protocol SILworX First Steps Introduction to SILworX using the HIMax system a...

Страница 7: ...position Safety notes and operating tips are particularly marked 1 3 1 Safety Notes The safety notes are represented as described below These notes must absolutely be observed to reduce the risk to a...

Страница 8: ...E Rev 2 00 1 3 2 Operating Tips Additional information is structured as presented in the following example i The text corresponding to the additional information is located here Useful tips and trick...

Страница 9: ...n accordance with IEC EN 61131 2 Ambient temperature 0 60 C Storage temperature 40 85 C Pollution Pollution degree II in accordance with IEC EN 61131 2 Altitude 2000 m Housing Standard IP20 Supply vol...

Страница 10: ...the user program Faults related to the wiring 2 3 Safety Precautions Observe all local safety requirements and use the protective equipment required on site 2 4 Emergency Information A HIMatrix system...

Страница 11: ...the inputs are safely transmitted to the connected controller via safeethernet The outputs are safely assigned their values by the connected controller via safeethernet 3 1 1 Safety Related Digital In...

Страница 12: ...ts DI of the same system as follows DI 3 DO 1 DI 1 1 2 2 2 4 EMERGENCY STOP 1 EMERGENCY STOP 2 EMERGENCY STOP switches in accordance with EN 60947 5 1 and EN 60947 5 5 Figure 2 Line Control The remote...

Страница 13: ...e 16 If an overload occurs one or all digital outputs are switched off If the overload is removed the outputs are switched on again automatically see Table 13 The external wire of an output is not mon...

Страница 14: ...ts a faulty signal on a digital output the affected module output is set to the safe de energized state using the safety switches If a device fault occurs all digital outputs are switched off In both...

Страница 15: ...ture 0 60 C for SILworX programming tool F3 DIO 20 8 021 SILworX 20 C Remote I O 20 digital inputs 8 digital outputs Operating temperature 20 60 C for SILworX programming tool F3 DIO 20 8 023 SILworX...

Страница 16: ...5 E Rev 2 00 3 3 Type Label The type plate contains the following details Product name Bar code 1D or 2D code Part no Production year Hardware revision index HW Rev Firmware revision index FW Rev Oper...

Страница 17: ...7 of 48 3 4 Assembly This chapter describes the layout and function of the remote I Os and their communication via safeethernet DIO 20 8 02 Figure 5 Front View Digital Inputs Safety Related Processor...

Страница 18: ...linking If ERROR blinks and all others LEDs are lit simultaneously the boot loader has detected an operating system fault in the flash memory and waits for a new operating system to be loaded ERROR Re...

Страница 19: ...ion Blinking Collision Green Off Half duplex operation no collision On Connection available Blinking Interface activity Yellow Off No connection available Table 7 Ethernet Indicators 3 4 1 4 I O LEDs...

Страница 20: ...ousing Refer to Chapter 3 4 1 3 for a description of the LEDs function The connection parameters are read based on the MAC address media access control address defined during manufacturing The MAC add...

Страница 21: ...ngaged using a suitable pin made of insulating material to avoid short circuits within the remote I O The reset is only effective if the remote I O is rebooted switched off and on while the key is sim...

Страница 22: ...lly separated High level Voltage Current input 15 30 VDC 2 mA at 15 V Low level Voltage Current input max 5 VDC max 1 5 mA 1 mA at 5 V Switching point typ 7 5 V Supply 5 x 20 V 100 mA at 24 V short ci...

Страница 23: ...on the ambient temperature Ambient temperature Output current 50 C 2 A 50 60 C 1 A 60 C 0 5 A Weight approx 1 2 kg Table 15 Product Data of F3 DIO 20 8 023 The remote I O F3 DIO 20 8 023 meets increa...

Страница 24: ...ories Inc ANSI UL 508 NFPA 70 Industrial Control Equipment CSA C22 2 No 142 UL 1998 Software Programmable Components NFPA 79 Electrical Standard for Industrial Machinery IEC 61508 FM Approvals Class I...

Страница 25: ...nnecting the Digital Inputs Use the following terminals to connect the digital inputs Terminal Designation Function inputs 13 LS Sensor supply of the inputs 1 4 14 1 Digital input 1 15 2 Digital input...

Страница 26: ...iggered with a corresponding delay i The measures specified above are not necessary if the plant design precludes surges from occurring within the system In particular the design must include protecti...

Страница 27: ...ble plugs Four poles screw terminals Wire cross section 0 2 2 5 mm2 single wire 0 2 2 5 mm2 finely stranded 0 2 2 5 mm2 with wire end ferrule Stripping length 10 mm Screwdriver Slotted 0 6 x 3 5 mm Ti...

Страница 28: ...oller is under voltage 2 The enclosure in use must be able to safely dissipate the generated heat Depending on the output load and supply voltage the HIMatrix F3 DIO 20 8 02 has a power dissipation ra...

Страница 29: ...iguration with SILworX In the Hardware Editor the remote I Os are represented like a base plate equipped with the following modules Processor module CPU Input module DI 20 Output module DO 8 Double cl...

Страница 30: ...module slot SC OC1 detection set the value to 1 DI Pulse Delay s UINT W Waiting time for line control detection of short circuits or cross circuits DI Error Code WORD R Error codes for all digital in...

Страница 31: ...ult in the digital input module 0x10 Short circuit of the channel 0x80 Intermittence between pulsed output DO and digital input DI e g Open circuit Open switch L undervoltage Value BOOL BOOL R Input v...

Страница 32: ...down test of the outputs faulty 0x0040 Active shutdown via WD faulty 0x0200 All outputs are switched off total current exceeded 0x0400 FTT test 1st temperature threshold exceeded 0x0800 FTT test 2nd t...

Страница 33: ...scription 0x01 Fault in the digital output module 0x02 Channel shutdown due to overload 0x04 Error while reading back the digital outputs 0x08 Error while reading back the status of the digital output...

Страница 34: ...stem manual for compact systems or the online help for more details The following chapter describes the system signals used for assigning signals in the remote I O 4 4 2 Signals and Error Codes for th...

Страница 35: ...faulty DI xx Error Code BYTE R Error codes for the digital input channels Coding Description 0x01 Fault in the digital input module 0x10 Short circuit of the channel 0x80 Intermittence between pulsed...

Страница 36: ...345 E Rev 2 00 System signal R W Description DI Pulse Delay 10E 6s UINT W Waiting time for line control detection of short circuits or cross circuits 1 SC OC SC short circuit OC open circuit Table 26...

Страница 37: ...of safety shutdown returns a fault 0x0004 Test of auxiliary voltage returns a fault 0x0008 FTT test of test pattern faulty 0x0010 Output switch test pattern faulty 0x0020 Output switch test pattern sh...

Страница 38: ...together with a controller No specific monitoring is required for remote I Os 5 1 Handling Handling of the remote I O during operation is not required 5 2 Diagnosis A first diagnosis results from eval...

Страница 39: ...ergized safe state The evaluation of diagnostics provides information on the fault cause 6 2 Maintenance Measures The following measures are required for the device Loading the operating system if a n...

Страница 40: ...0 8 02 Page 40 of 48 HI 800 345 E Rev 2 00 7 Decommissioning Remove the supply voltage to decommission the device Afterwards pull out the pluggable screw terminal connector blocks for inputs and outpu...

Страница 41: ...d mechanical damage HIMatrix components must be transported in packaging Always store HIMatrix components in their original product packaging This packaging also provides protection against electrosta...

Страница 42: ...45 E Rev 2 00 9 Disposal Industrial customers are responsible for correctly disposing of decommissioned HIMatrix hardware Upon request a disposal agreement can be arranged with HIMA All materials must...

Страница 43: ...th PELV Protective extra low voltage PES Programmable electronic system R Read The system variable or signal provides value e g to the user program Rack ID Base plate identification number Interferenc...

Страница 44: ...1 Connections to Safety Related Digital Inputs 11 Figure 2 Line Control 12 Figure 3 Connection of Actuators to Digital Outputs 13 Figure 4 Sample Type Label 16 Figure 5 Front View 17 Figure 6 Block D...

Страница 45: ...Data F3 DIO 20 8 021 20 C 23 Table 15 Product Data of F3 DIO 20 8 023 23 Table 16 Product Data of F3 DIO 20 8 024 23 Table 17 Certificates 24 Table 18 Terminal Assignment for the Digital Inputs 26 Ta...

Страница 46: ...6 of 48 HI 800 345 E Rev 2 00 Index block diagram 17 diagnosis 38 fault reaction digital inputs 12 digital outputs 14 front view 17 line control 12 reset key 21 safeethernet 20 safety function 11 spec...

Страница 47: ......

Страница 48: ...334 HIMA Paul Hildebrandt GmbH Co KG P O Box 1261 68777 Br hl Germany Phone 49 6202 709 0 Fax 49 6202 709 107 E mail info hima com Internet www hima com HI 800 345 E by HIMA Paul Hildebrandt GmbH Co K...

Отзывы: