S-BT-ER, S-BT-EF
Single point connection
Lightning protection
For high temporary current due to lightning.
Classification N
(acc. IEC 62561-1)
Classification H
(acc. IEC 62561-1)
Type A
Recommended electrical
connectors:
S-BT-ER M10/15 SN 6
S-BT-ER W10/15 SN 6
S-BT-EF M10/15 AN 6
S-BT-EF W10/15 AN 6
S-BT-ER M8/15 SN 6
S-BT-EF M8/15 AN 6
S-BT-ER M10 HC 35*)
S-BT-ER W10 HC AWG2*)
S-BT-EF M10 HC 35*)
S-BT-EF W10 HC AWG2*)
S-BT-ER M10 HC 120
S-BT-ER W10 HC AWG4/0
S-BT-EF M10 HC 120
S-BT-EF W10 HC AWG4/0
Recommended electrical
connectors:
S-BT-ER M10 HC 35*)
S-BT-ER W10 HC AWG2*)
S-BT-EF M10 HC 35*)
S-BT-EF W10 HC AWG2*)
S-BT-ER M10 HC 120
S-BT-ER W10 HC AWG4/0
S-BT-EF M10 HC 120
S-BT-EF W10 HC AWG4/0
Maximum lightning current
I
imp
= 50 kA for
≤
5 ms
(according to IEC 62561-1)
I
imp
= 100 kA for
≤
5 ms
(according to IEC 62561-1)
Note:
• Recommended maximal cross section of connected cable
according
IEC 60947-7-2 and IEC 60947-7-1:
16 mm² (6 AWG) copper (tested short circuit current I
cw
= 1.92 kA for 1 s)
• Fastening of thicker cable is acceptable, if the maximum short circuit current I
cw
and
the exposure time is not exceeded and the provisions on cable lug thickness t
cl
are
observed.
*) this items are available only on special request