Hilti Hit-hY 70 Скачать руководство пользователя страница 7

Adhesive Anchoring Systems

3.2.6 HIT-HY 70 Hybrid for Masonry Construction

220   Hilti, Inc. (US) 1-800-879-8000  |  www.us.hilti.com  I  en español 1-800-879-5000  I  Hilti (Canada) Corp. 1-800-363-4458  I  www.hilti.ca  I  Anchor Fastening Technical Guide 2016

Table 11 - HIT-HY 70 allowable adhesive bond loads for HIT-IC inserts in the face of hollow brick

1, 2, 3, 4, 5, 10

Thread 

size

Effective 

embedment

Tension 

Minimum edge 

distance c

min

Load 

reduction 

factor @ c

min

Shear

Edge distance

6

Critical c

cr

Minimum c

min

Load reduction 

factor @ c

min

in.

(mm)

6

lb (kN)

7, 8

in.

(mm)

9

lb

(kN)

7, 8

in.

(mm)

in.

(mm)

#14 Screw 

2

(51)

170 (0.8)

8

(203)

1.00

222 (1.0)

12

(304.8)

8

(203)

1.00

5/16-18 UNC

3-1/8 (79)

880 (3.9)

650 (2.9)

1.00

3/8-16 UNC

880 (3.9)

1,290 (5.7)

0.63

1/2-13 UNC

990 (4.4)

1,780 (7.9)

0.47

1  All values are for anchors installed in hollow brick masonry with minimum masonry prism strength of 3,000 psi. Hollow brick units shall be conforming to ASTM C652.  

Allowable loads are calculated using a safety factor of 5.

2  Anchors shall be installed in the face of the hollow brick masonry wall.

3  Anchors are not recognized for resisting earthquake forces. For short-term loading due to wind forces, the allowable loads shall not be increased.
4  Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with figure 12.

5  Tabulated embedment depth is limited by the length of the plastic HIT-SC screens.
6  Tabulated values are for one anchor installed in any location of the brick wall including the horizontal and head mortar joints.
7  One anchor shall be permitted to be installed in each brick. Two anchors may be spaced as close as the lesser of 2 bricks or 8 in. apart without any load reduction.
8  Allowable loads must be the lesser of the adjusted masonry or bond tabulated above and the steel values given in table 4.
9  The critical edge distance, c

cr,

 is the edge distance where full load values in the table may be used. The minimum edge distance, c

min

, is the minimum edge distance for which 

values are available and installation is recommended. Edge distance is measured from the center of the anchor to the closest edge.

10 For combined loading: (T

applied

 / T

allowable

) + (V

applied

 / V

allowable

) ≤ 1

Table 10 - HIT-HY 70 allowable adhesive bond loads for threaded rods in the face of hollow brick

1, 2, 3, 4, 5, 10

Nominal 

anchor 

diameter

Effective 

embedment

Tension 

Minimum edge 

distance c

min

Load 

reduction 

factor @ c

min

Shear

Edge distance

6

Critical c

cr

Minimum c

min

Load reduction 

factor @ c

min

in.

(mm)

6

lb (kN)

7, 8

in.

(mm)

9

lb

(kN)

7, 8

in.

(mm)

in.

(mm)

1/4

3-1/8 (79)

530 (2.4)

8

(203)

1.00

370 (1.6)

12 (304.8)

8

(203)

1.00

5/16

735 (3.3)

595 (2.6)

1.00

3/8

905 (4.0)

1,045 (4.7)

0.76

1/2

905 (4.0)

1,685 (7.5)

0.52

Table 12 - HIT-HY 70 allowable adhesive bond loads for threaded rods in multi-wythe solid brick walls

1, 2, 3, 4, 5, 6, 8

Nominal 

anchor 

diameter

Effective 

embedment

7

Tension

Shear

Minimum 

spacing s

min

Edge distance

6

Critical c

cr

Minimum c

min

Load reduction 

factor @ c

min

in.

(mm)

lb

(kN)

lb

(kN)

in.

(mm)

in.

(mm)

in.

(mm)

3/8

6

(152)

895

(4.0)

680

(3.0)

16

(406)

16

(406)

8

(203)

0.5

10

(254)

1,325

(5.9)

795

(3.5)

1/2

6

(152)

895

(4.0)

1,075

(4.8)

10

(254)

1,455

(6.5)

1,115

(5.0)

5/8

6

(152)

1,025

(4.6)

1,405

(6.3)

10

(254)

1,955

(8.7)

1,445

(6.4)

3/4

8

(203)

1,575

(7.0)

1,985

(8.8)

13

(330)

2,135

(9.5)

1,985

(8.8)

1  All values are based on mortar shear strength of 45 psi or greater. Allowable loads are calculated using a safety factor of 5.
2  Anchors must be installed in the face of the multi-wythe URM wall. The wall must have a minimum thickness of 13 inches representing 3 wythes of brick..
3  Tabulated values are for maximum one anchor installed in the center of the brick of the multi-wythe URM wall.

4  Edge distance, c

min

, and spacing, s

min

, are the minimum distances for which values are available and installation is recommended. Edge distance is measured from the center of 

the anchor to the closest edge. Spacing is measured from the center of one anchor to the center of an adjacent anchor.

5  Allowable loads must be the lesser of the adjusted masonry or bond tabulated values and the steel values given in table 4.

6  Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with figure 12.

7  Tabulated embedment depth is limited by the length of the plastic HIT-SC screens.
8  For combined loading: (T

applied

 / T

allowable

) + (V

applied

 / V

allowable

) ≤ 1

d

o

h

o

h

ef

Figure 8 - HIT-HY 70 specifications 

for rebar in multi-wythe brick wall

d

o

h

o

h

ef

Figure 7 - HIT-HY 70 specifications for 

HAS rods in multi-wythe brick wall

Содержание Hit-hY 70

Страница 1: ...luding data development product specifications general suitability installation corrosion and spacing and edge distance guidelines US http submittals us hilti com PTGVol2 CA http submittals us hilti com PTGVol2CA To consult directly with a team member regarding our anchor fastening products contact Hilti s team of technical support specialists between the hours of 7 00am 6 00pm CST US 877 749 6337...

Страница 2: ...ds steel internally threaded inserts combi inserts reinforcing bars plastic mesh screen tubes for installation only in unreinforced masonry URM hollow concrete block and hollow brick walls and the HIT HY 70 Adhesive For clay tile terracotta and masonry applications that are not specifically addressed in this Technical Guide please contact Hilti Technical Services Guide Specifications Master Format...

Страница 3: ...sonry cell 3 Linear interpolation of load values between minimum spacing smin and critical spacing scr and between minimum edge distance cmin and critical edge distance ccr is permitted 4 Concrete masonry thickness must be equal to or greater than 1 5 times the anchor embedment depth EXCEPTION the 5 8 inch and the 3 4 inch diameter anchors No 5 and No 6 bars may be installed in minimum nominally 8...

Страница 4: ...nforcing bars in the top of grout filled concrete masonry walls1 2 3 4 5 6 Nominal anchor diameter or rebar size Effective embedment in mm Edge distance in mm 7 8 Minimum end distance in mm Tension lb kN Shear load lb kN 9 Load parallel to edge of masonry wall Load perpendicular to edge of masonry wall 1 2 4 1 2 114 1 3 4 44 5 8 203 1 165 5 2 815 3 6 345 1 5 4 101 6 1 625 7 2 1 445 6 4 505 2 3 5 8...

Страница 5: ...onry 5 When using the basic load combinations in accordance with IBC Section 1605 3 1 tabulated allowable loads must not be increased for seismic or wind loading When using the alternative basic load combinations in IBC Section 1605 3 2 that include seismic or wind loads tabulated allowable loads may be increased by 33 1 3 percent or the alternative basic load combinations may be reduced by a fact...

Страница 6: ...concrete block wall A maximum of two anchors for each cell of the hollow ungrouted concrete block is allowed 3 Anchors are not recognized for resisting earthquake forces For short term loading due to wind forces the allowable loads shall not be increased 4 Tabulated allowable loads shall be adjusted for increased base material temperatures in accordance with figure 12 5 Tabulated embedment depth i...

Страница 7: ...combined loading Tapplied Tallowable Vapplied Vallowable 1 Table 10 HIT HY 70 allowable adhesive bond loads for threaded rods in the face of hollow brick1 2 3 4 5 10 Nominal anchor diameter Effective embedment Tension Minimum edge distance cmin Load reduction factor cmin Shear Edge distance6 Critical ccr Minimum cmin Load reduction factor cmin in mm 6 lb kN 7 8 in mm 9 lb kN 7 8 in mm in mm 1 4 3 ...

Страница 8: ...onfigurations on site testing is required to determine the actual performance of the anchor Allowable loads are calculated using a safety factor of 5 2 Tabulated embedment depth is limited by the length of the plastic HIT SC 16x50 mm screens See figure 11 3 The required concrete thickness is the thickness for which values are available and installation is recommended Anchors shall be installed alo...

Страница 9: ... 30 min 20 min 10 min 7 min 4 min 2 min 1 min 5 6 10 11 20 21 30 31 40 41 42 50 51 68 69 86 87 104 10 min 10 min 7 min 4 min 2 min 1 min 23 32 33 41 42 50 51 68 69 86 87 104 5 0 1 5 6 10 11 20 21 30 31 40 3 2 6 4 Installation instructions Installation Instructions For Use IFU are included with each product package They can also be viewed or downloaded online at www us hilti com US and www hilti ca...

Страница 10: ...hollow concrete block Threaded Rod Mesh Sleeve Approximate fastenings per foil pack1 Rod Size 5 8 Grade Embedment in Qty Nominal Bit Dia in Mesh Sleeve per Fastening 11 1 fl oz 330 ml 16 9 fl oz 500 ml Plastic Sleeve for 14 screw 2 20 1 2 1 HIT S 12 I 25 40 HAS B 1 4 x 3 2 20 1 2 1 SC 12x50 25 40 HAS B 1 4 x 4 1 2 3 1 8 20 1 2 1 SC 12x85 16 26 HAS B 5 16 x 3 2 20 5 8 1 SC 16x50 16 26 HAS B 5 16 x ...

Страница 11: ... 2 In hollow material use with HIT SC 22 x 50 10 7 8 13 Internally Threaded HIT IC 1 2 3 x 3 16 In hollow material use with HIT SC 22 x 85 10 7 8 13 HIT Combi Insert HIT S 12 I Plastic sleeve for 14 screw 20 1 2 Multi wythe brick walls Threaded Rod Mesh Sleeve Approximate fastenings per foil pack1 Rod Size 5 8 Grade Embedment in Qty Bit Diameter in Mesh Sleeve per Fastening 11 1 fl oz 330 ml 16 9 ...

Отзывы: