Thermal Network Speed dome·Quick Start Guide
5
2.3
Alarm In/Out Connections
This section is only for the speed dome with alarm in/out functions.
The speed dome can be connected with alarm inputs (0~5VDC) and alarm
outputs. Refer to the following diagrams for alarm output:
JQC-3FG
Relay
30VDC
GND OUT
L
N
~
220V AC
Relay Output
(10A 250VAC )
Diagram (left)
Diagram (right)
1A
OUT(n)
OUT(n)
+
-
DC
DC Load
Relay Output
Positioning System OUT(n)
OUT(n)
Positioning System
Figure 2-3
Alarm Out Connections
The alarm provides the relay output (no voltage), and the external power supply is
required when it connects to the alarm device.
For DC power supply (left diagram), the input voltage must be no more than
30VDC, 1A.
For AC power supply, the external relay must be used (right diagram) to
prevent damages to the speed dome and avoid risk of electric shock.