Page: 25
6.3.3
Adding the External Tag Reader (From the Engineer Menu)
Enter the engineers menu and scroll to 'ASSIGN KEYPADS/READERS' and press
. Please see the Programming
Manual for more information.
6.3.4
Connecting a Mag Lock and a Request to Exit Button to the External Tag Reader
The diagram show the relay mag lock control switching positive and shows a normally open request to exit
button, and takes “0V” from the control panel.
6.3.5
Connecting Door Monitoring and Door Alarm Monitoring to the External Tag Reader
Connecting Door Monitoring:
Use the white and grey wire. The door monitor input needs to be programmed as
the first input number of the reader address (programmed as ‘Final Exit’). If the door contact is forced open
without presenting a valid tag or pressing the push to exit button, then the panel will go into an alarm.
NOTE:
The DEOL values must be 4K7, 2K2 as shown. This does not affect the control panel DEOL values.
Connecting Door Alarm Monitoring:
Use the purple wire. When the door monitor exceeds the door open time or
if the door is forced open then the alarm PGM will generate an alarm. The input at the control panel should be
programmed as ‘Day Alarm’ and the attribute programmed as “Normally Open”.
Input Resistance:
4k7 / 2k2 DEOL Range
Normal: 1k4 to 2k9
Burglary Alarm: 4k2 to 7k8
Tamper: <1k4 or >22k
NOTE:
The resistance values are
fixed to 4K7 Alarm and 2K2 Tamper
in the EUR-108X Reader