Rev. F 01-2022
12
MTEC.5811.GB-F-1 Operation and maintenance manual HHA series English
HHA
,QGXVWULDOGHKXPLGL¿HUV
3.1 Unit description
The dehumidifers are high-performances units especially designed for industrial or commercial purposes where humidity level should be
controlled or water vapor condensation should be prevented. These units are particularly indicated for archives, ironing rooms, bookstores,
cheese factories, underground rooms, cellars and industrial sites where high humidity level is present. This series comprises 8 models
which cover a capacity range from 49 to 530 l/24h. The units are designed for easy maintenance and service, each part being readily ac-
cessible and, when required, easily replaceable thus reducing service and maintenance costs. The units from size 50 to 200 are supplied
with a solenoid valves set for the hot gas injection used to defrost the evaporator in case of severe working conditions.
3.1.1 Frame
All units are made from hot-galvanised thick sheet metal, painted with polyurethane powder enamel at 180°C to ensure the best resistance
against the atmospheric agents. The frame is self-supporting with removable panels. All screws and rivets are in stainless steel. The colour
of the units is RAL 9018.
5HIULJHUDQWFLUFXLW
The refrigerant gas used in these units is R410A. The refrigerant circuit is made by using international primary brands components and
according to ISO 97/23 concerning welding procedures.
7KHUHIULJHUDQWFLUFXLWLQFOXGHVVLJKWJODVV¿OWHUGULHUWKHUPDOH[SDQVLRQYDOYHZLWKH[WHUQDOHTXDOL]HU6FKUDGHUYDOYHVIRUPPDLQWHQDQFH
and control, pressure safety device (according to PED regulation).
3.1.3 Compressors
The compressors are rotative type, with thermal overload protection by a klixon embedded in the motor winding. The compressor is
mounted on rubber vibration dampers and it is supplied,standard, with sound-proof cover to reduce noise emission. The inspection is pos-
sible through the frontal panel of the unit that allows the maintenance of the compressor.
3.1.4 Condenser and evaporator
Condensers
DQGHYDSRUDWRUVDUHPDGHRIFRSSHUSLSHVDQGDOXPLQLXP¿QV
All evaporators are painted with epoxy powders to prevent corrosion problem due to their use in aggressive environments. The diameter of
WKHFRSSHUSLSHVLV´DQGWKHWKLFNQHVVRIWKHDOXPLQLXP¿QVLVPP7KHWXEHVDUHPHFKDQLFDOO\H[SDQGHGLQWRWKHDOXPLQLXP¿QV
to improve the heat exchange factor. The geometry of these heat exchangers guarantees a low air side pressure drop and then the use of
low rotation (and low noise emission) fans.
All units are supplied, standard, with a stainless steel drip tray and all evaporators are supplied with a temperature sensor used as automatic
defrost probe.
3.1.5 Supply fan
The fans are made of galvanized steel, centrifugal type. It is statically and dynamically balanced and supplied.
The electric motors are directly connected to the fan; they are all at 3 speeds, with integrated therma protection. The protection class of the
motors is IP 54.
$LUÀOWHU
It i
VPDGHRIV\QWKHWLF¿OWHULQJPHGLDXQGXODWHGW\SHZLWKRXWHOHFWURVWDWLFFKDUJHWKH\DUHDOOUHPRYDEOHIRUGLIIHUHQWLDOGLVSRVDO(I¿FLHQF\
class M5, according to EN 779:2012.
3.1.7 Microprocessors
All units are supplied standard with microprocessor controls. The microprocessor controls the following functions: regulation of the water
temperature, antifreeze protection, compressor timing, compressor automatic starting sequence, alarm reset, potential free contact for
remote general alarm, alarms and operation leds.
3.1.8 Electric enclosure
The electric switch board is made according to electromagnetic compatibility norms CEE 73/23 and 89/336. The accessibility to the board is
possible after removing the front panel of the unit and the OFF positioning of the main switch. The following components are also standard
installed: main switch, magnetic-thermal switches (as a protection fans and compressors), control circuit automatic breakers, compressor
contactors, fan contactors. The terminal board is supplied with voltage free contacts for remote ON-OFF and general alarm.
3.1.9 Control and protection devices
All units are supplied with the following control and protection devices: antifreeze protection sensor, high pressure switch with manual
3. TECHNICAL CHARACTERISTICS