USER'S GUIDE R18 AXIAL FAN , Iss: 6.05.2021

07

DIAGNOSTICS & TROUBLESHOOTING

Fan does not start or run - alarm rele status OPEN or FLASHES:
Possible causes: missing power (no line voltage), low voltage (under 185V), extremely thermally or mechanically overloaded or fan failure (short circuit
of electronic or windings).
Check line voltage, check value and polarity of control signal, check that rotor is free to rotate.

Fan does not start or run - alarm rele status CLOSE:
Possible causes: missing or inadequate control signal.
Check value and polarity of control signal.

Fan runs with half of desired speed - alarm rele status CLOSE:
Possible causes: Low supply voltage, inadequate control signal or fan overheating.
Check line voltage, check control signal, check temperature and sufficient airflow of cooling air or loss of motor cooling.

Attention !

In the event of fan failure is detected (short/open in circuit of electronics/windings), never try to repair the fan, but replace it with new one or/and return
defected fan to the manufacturer for repair or replacement.

ALARM RELAY DIAGNOSTICS

Alarm relay contact OPEN on ERROR. Alarm relay contacts capability: max. 2A-250VAC cos fi0.6, max. 3A-30VDC.
Errors on which alarm relay OPEN:
- Rotor locked in duration exceeding 10s.

- Motor winding overheating.
- Power module overheating.
- DC link undervoltage.
- Internal communication error.

The alarm relay needs approximately 3-4 seconds after switching on the line voltage to become operable - change contacts to status CLOSE if no
malfunction is detected.

MULTI COLOUR LED DIAGNOSTICS

GREEN STATUS: 

- NO malfunction is detected.

ORANGE STATUS:

- Missing controll signal (if function 'Emergency operation' is active).
- Electronics / Motor / Power module high temperature.
- Break active.

RED STATUS: 

- Rotor locked.
- Motor overheating.
- Power module overheating.
- DC link undervoltage error.
- Internal communication error.

© Copyright  HIDRIA d.o.o., All rights reserved. Document is subject to change without prior notification.

9 / 10

Содержание 0318-4-1006

Страница 1: ...ROHS AND EMC DIRECTIVES 12 SERVICE ADDRESSES AND ADDITIONAL DATA This document contains instructions and information for the operation installation connection use and maintenance of the product Be sur...

Страница 2: ...rm Do not operate this appliance in an explosive atmosphere Fan must be fixed to stationary housing with appropriate screws according to this guide This appliance is not intended to be built as a part...

Страница 3: ...not intended to be built as a partition fan mounting in outside windows or walls unless it is built into an end application which is designed for that purpose The fan is intended to be permanently co...

Страница 4: ...ensing Max pressure 250 Pa ErP DATA Overall Efficiency Effes 54 3 Installation category A Efficiency category static Efficiency grade N 57 7 Variable speed drive INTEGRATED Power Input Pelec 2917 9 W...

Страница 5: ...juries the height and the diameter of inlet cone must be appropriate dimensions To lift the device with lifting devices use the hangers provided for this purpose as shown on figure below Always use su...

Страница 6: ...ng plug must remain in the gland Connection box screws have to be tightened with torque of 2 0Nm 2 5Nm Secure connection cable to the fan guard grill or to the motor holder with cable fasteners so tha...

Страница 7: ...but the highest system pressure reached at maximum load is 16Bar 8V For optimal operation of the application the fan mounted on a condenser should run at max speed at 8V of input control voltage In o...

Страница 8: ...correct value the motor will restart automatically In the specific case the undervoltage protection may switch off the fan to stand by mode for example fan running or testing at high pressure drop an...

Страница 9: ...in circuit of electronics windings never try to repair the fan but replace it with new one or and return defected fan to the manufacturer for repair or replacement ALARM RELAY DIAGNOSTICS Alarm relay...

Страница 10: ...protection grill Do not apply any force for the cable s When transporting fans mounted on final units apparatus take care that they are properly secured and don t touch other devices which are transp...

Отзывы: