background image

www.hi-velocity.com

© 1995-2020 Energy Saving Products Ltd.

© 1995-2020 Energy Saving Products Ltd.

The Return Air is to be sized on a 0.15 static pressure (37 pa) as 

compared to 0.10 static pressure (25 pa) for conventional forced 

air systems. The maximum length for an individual return air duct 

is fifty feet (15.24m).

Duct Sizing

Please  note:    It  is  VERY  important  NOT 

to  undersize  the  return  air,  as  this  will 

create  noise,  increase  motor  power 

consumption, reduce airflow and increase 

the possibility of condensate carry-over.

Table 03 has recommended return air sizes for round and 

rectangular ducts. A variance of

 

+20% 

is allowable for sizing 

return ducts that connect to the RBM or Hi-Velocity Systems unit. 

Where allowed by local codes, a single return air grill may be 

used. Note:  Return air grill must have equal minimum of free air 

area to return air.

Table 03 – Return Air Duct Sizes

Unit

Rigid Ø

Flex Ø

 Min Sq. 

Inches 

(Sq. cm)

50/51/52

12” 

(305mm)

14” 

(356mm)

120

(774cm)

70/71

12” 

(305mm)

14” 

(356mm)

120

(774cm)

100/101

14” 

(356mm)

16” 

(406mm)

168 

(1084cm)

Remember:  When  using  flexible  duct  for  return  air,  use 

one duct size larger due to the higher friction loss.

Important:    When  connecting  a  round 

Return  Air  to  the  RBM  coil,  a  round  to 

rectangular transition is required.

Specifications

RBM-50

RBM-70

RBM-100

Matching Fan Coil

HE-Z/HE-B/HE-50/51

HV-50/51/52

CU-51

LV-50

HE-Z/HE-B/HE/HV-70/71

LV-70

HE-Z/HE-P/HE-B/HE/HV-100/101

Part Number

41090300050

41090300070

41090300100

Tons

(1)

1.5 - 2.0 

(5.3 - 7.0 kW)

2.5 - 3.0

 

(8.8 - 10.6 kW)

3.5 - 5.0

 (12.3 - 17.6 kW)

Refrigerant Type

R-410A

R-410A

R-410A

TX Cooling MBH

(2) 

   

 

18-24

 (5.3-7.0 kW)

30-36

 (8.8-10.6 kW)

42-60

 (12.3-17.6 kW)

Latent Cooling MBH

6.8-8.9

 (2.0-2.6 kW)

11.7-13.7

 (3.4-4.0 kW)

16.0-22.2

 (4.7-6.5 kW)

Fin Material

Aluminum

Aluminum

Aluminum

Tubing Material

Copper

Copper

Copper

Type of Fins

.006 Al 

(0.1524mm)

.006 Al 

(0.1524mm)

.006 Al 

(0.1524mm)

Connection 

Sizes

Liquid Line (Lq)

3/8

” 

(9.5mm)

3/8

” 

(9.5mm)

3/8

 

(9.5mm)

Suction Line (S)

7/8

 (22.3mm)

7/8

 (22.3mm)

7/8

 (22.3mm)

Drain Connection

3/4

” 

M CPVC

 

(19mm)

3/4

 

M CPVC

 

(19mm)

3/4

” 

M CPVC

 

(19mm)

TXV with Built in Check Valve & Bypass

Pre-Installed

Pre-Installed

Pre-Installed

Access Ports

Yes

Yes

Yes

Freeze Stat

Yes

Yes

Yes

Shipping Weight

35 lbs

 

(15.9 kg)

45 lbs

 

(20.4 kg)

55 lbs

 

(24.9 kg)

Module Size (L x W x H)

14 

1

⁄2

 x 18 

1

⁄4

 x 18 

1

⁄4

(368mm x 464mm x 464mm)

19 

1

⁄2

 x 18 

1

⁄4

 x 18 

1

⁄4

(495mm x 464mm x 464mm)

25 

1

⁄2

 x 18 

1

⁄4

 x 18 

1

⁄4

(648mm x 464mm x 464mm)

-9-

-9-

Important:  When using flexible duct for 

return air, use one duct size larger due to 

the higher friction loss.

Module RBM

RBM Refrigerant Base Module Installation

(2) Smaller condensers may be matched to the fan coil when needed (match TXV to condenser size)

(1) Minimum of

Minimum of

 four HE outlets

 four HE outlets

 per ton of cooling needed. (2” Duct = Minimum 

 per ton of cooling needed. (2” Duct = Minimum 

eight outlets

eight outlets

 per ton)

 per ton)

MBH - Thousand British Thermal Units per Hour

TX - Thermal Expansion

TXV - Thermal Expansion Valve

Содержание RBM-100

Страница 1: ...e Installation 052020 RBM Refrigerant Base Module Installation Manual Small Duct High Velocity Heating Cooling and Home Comfort Systems RBM 50 1 5 2 Tons RBM 70 2 5 3 Tons RBM 100 3 5 5 Tons Includes Pre Piped TXV Freeze Stat Service Access Ports T Mounting Brackets Double Sided Mounting Tape Hole Plugs 2 ...

Страница 2: ......

Страница 3: ...es can be used on any R 410A condenser if R 410A refrigerant components are used All Energy Saving Products R Series modules come standard with R 410A refrigerant components 3 3 The RBM module can be installed as a stand return air base for the fan coil or as a side mounted coil When the desired air inlet side has been determined the module can be adapted The module comes ready as left to up right...

Страница 4: ...e unit 90 deg clockwise Fig 07 Fig 07 6 Replace the drain pan in new bottom location Fig 09 Fig 09 Fig 06 3 Slide out the air flow deflector plate Fig 06 Fig 08 5 Slide the air flow deflector plate back into the section it was removed from in the new orientation Fig 08 Fig 10 7 Remove round knock outs on the door to fit drain lines Plug previously used drain holes with provided plugs Fig 10 Insert...

Страница 5: ... should always be used to make the first cut For this first cut do not use a saw blade longer than 5 125mm or damage to the coil can occur Return Air Cutouts Mounting Brackets Fig 12 TO AVOID DAMAGE After the first initial cut using the return air knockout s a metal shear must be used to make the return air cutout opening match more closely to the filter or return air ducting size to maximize flow...

Страница 6: ...ring needs arise in which the outdoor unit is controlled through another means of wiring the Freeze Stat should be connected in series on the input side of the control wiring Refrigerant Bypass All RBM coils come with a pre installed check valve ready TX valve used for AC only or heat pump condensing units Third party TX valves may require a bypass check valve Fig 14 Bypass check valve 6 6 Freeze ...

Страница 7: ...eck local codes Run the proper size copper wires to the unit and connect as per the manufacturer s recommendations Ensure that the unit is setup for a TX system If not a hard start kit may be required Evacuating The system must be brazed under a nitrogen purge to prevent oxidation of the pipe during the brazing process After the piping is installed and all components have been brazed together a va...

Страница 8: ...ing brackets are located at the base of the unit for secure mounting The receiver is to be located on the liquid line of the system anywhere between the indoor and outdoor coils As the unit is of a bi flow design it does not matter which end faces towards the indoor coil The inlet outlet ports are constructed of steel and require the use of a 35 45 Silver Solder and Flux for brazing The use of sta...

Страница 9: ...HV 70 71 LV 70 HE Z HE P HE B HE HV 100 101 Part Number 41090300050 41090300070 41090300100 Tons 1 1 5 2 0 5 3 7 0 kW 2 5 3 0 8 8 10 6 kW 3 5 5 0 12 3 17 6 kW Refrigerant Type R 410A R 410A R 410A TX Cooling MBH 2 18 24 5 3 7 0 kW 30 36 8 8 10 6 kW 42 60 12 3 17 6 kW Latent Cooling MBH 6 8 8 9 2 0 2 6 kW 11 7 13 7 3 4 4 0 kW 16 0 22 2 4 7 6 5 kW Fin Material Aluminum Aluminum Aluminum Tubing Mater...

Страница 10: ...ain Conn Refrigerant Modules B C A D E F RBM 50 14 1 2 368mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM 70 19 1 2 495mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM 100 25 1 2 648mm 18 1 4 464mm 18 1 4 464mm 3 8 o d 7 8 o d 3 4 M CPVC RBM Series Sizing A B C D E F 10 10 Module RBM RBM Refrigerant Base Module Installation ...

Страница 11: ...and other products or materials furnished by the installer TERMS CONDITIONS Any repair performed under warranty must be approved by Energy Saving Products Ltd for this warranty to be valid This warranty replaces all other warranties expressed or implied www hi velocity com Should there be multiple consecutive failures of a single part warranty will not be considered unless a contractor has contact...

Страница 12: ...b Energy Saving Products prides itself on Customer Service and provides design services and contractor support For all of your Heating Cooling and Indoor Air Quality needs the Hi Velocity System is the right choice for you Phone 780 453 2093 Fax 780 453 1932 Toll Free 1 888 652 2219 www hi velocity com Hi Velocity HE Z Fan Coils Hi Velocity HE Z Fan Coils Green Green Technology Technology Build Sm...

Отзывы: