15
35
Description of signal inputs
Note!
Connect the signal inputs "MP", "HL", "LL", "HP", "LP", "STOP", "CO" and "PROG" only to
volt-free
contacts!
MP Motor protection
When using pumps which are equipped with a motor protection circuit breaker with a volt-free message contact, it is
possible to connect this switch to input "MP". The controller will then monitor and, according to the programming,
evaluate pump faults.
Type of connection in plant concepts with two pumps:
Function
Test time
Type of contact
Type of contact
connection
Action
S
Message contact of
an external motor
protection circuit
breaker
2 seconds
Normally closed
Serial connection
S
Switch off
S
Continuous alarm
S
Entry in error list
Normally open
Parallel connection
Please program the input "MP" according to the operating mode of the message contact:
"M"
BASIC PROGRAM
Funct. Motor prot.
HL and LL High and Low level
Connections for volt-free contacts
Function
Test time
Type of contact
Action
HL
S
Level transmitter input
"Full Level"
S
Pressure switch input
seconds
Normally closed 2
S
End production (with a connected
High level transmitter)
S
Start production (with a connected
pressure switch)
LL
S
Level transmitter input
"Low Level"
seconds
Normally open 2
S
Start production (with a connected
Low level transmitter)
The connections "HL" and "LL" can be used for controlling the production:
a) For plants with a storage tank:
As soon as the lower level "Tank empty" (connection "LL") has been
reached, the contact transmitter closes and the plant is switched on
("Production"). It is only switched off again if the upper level "Tank
full" (connection "HL") has been reached and this contact
transmitter opens.
It is also possible to use only an upper level transmitter (float switch)
or a remote control switch (Production/Standby) instead of two level
transmitters. In this case, the connection "LL" has to be connected
via a bridge with "
┴
". The
A
Run / Stop
@
key ("Production / Standby")
will then be without function.
Note!
If using automatic concentrate displacement via permeate (flush), observe that, depending on the pressure ratios, soft
water can still run into the storage tank until the end of the flushing duration. Due to this, the upper level transmitter has
to be arranged in a way that an tank overflow is avoided. For safety reasons, the tank should in any case have an tank
overflow to the drain. It is possible to install an level transmitter above the
A
Full level
A
in order to monitor the tank
overflow.
Connect this switch to the programmable signal input "PROG". The plant automatically switches off if the "Tank overflow
level" has been reached.
Note!
When operating the osmosis plant without a level transmitter (manual operation), a bridge has to be connected across
the connection
A
HL
A
. A bridging of the connection "LL" is
not
allowed.
b) For plants with one pressure switch or remote control switch:
Connect a bridge to the connection "LL" and the pressure switch to the connection "HL". The pressure switch must have
a normally closed contact.
Содержание Softmaster ROE 2
Страница 1: ...Softmaster7 ROE 2 Microprocessor controllers for reverse osmosis plants Operating instructions ...
Страница 31: ...31 35 Technical appendix Example for an osmosis plant layout ...
Страница 32: ...32 35 Connection example displayed relay position Device deenergized ...
Страница 33: ...33 35 Connection example for 24 V displayed relay position Device deenergized ...
Страница 34: ...34 35 Conformity Declaration ...