10/17

Manual desalination / TEST

For simulation, commissioning or testing purposes it is possible to manually open the desalination valve:
1.

Select the option “Manual desalination“ in the menu “Service” and open the desalination valve via the  “ENTER”
key.  The display “Des. val. OPEN” is shown until you exit the manual function via the ”ENTER” or “M” key and thus
close the desalination valve.

2.

Select the option “Auto desalination“ in the menu “Service” und start automatic desalination via the  “ENTER” key.
The display “Desalination” appears and the desalination valve remains open for the period programmed under
“Desalination time“. The menu is automatically exited after starting desalination and the operating display for the
current desalination appears.

In both cases the following occurs:

S

The volume memory for the quantity of water is set to 0.

S

The water meter impulses are still processed for dosing even 

during

 manual desalination, however, they are 

not

 added

up for the following desalination.

Termination of desalination

You can cancel/stop desalination at any time by pressing the “ENTER“ key in the operating display (not in the menu !) for
5 seconds; the valve will then close 

immediately (!)

.

Dosing

You can use the dosing valve or solenoid or motor dosing pumps. Select the
controller according to the requirements.

Single impulse

For the single impulse: The dosing output (relay K2) is switched for the set time
(duration of dosing impulse) once the programmed quantity of water has been
reached. Program the duration of the impulse between 0.2 and 9 seconds and 1 as
the number of impulses.

Multiple impulses

For multiple impulses: Impulses for the set time (duration of impulse) with the
programmed pauses are emitted once the programmed quantity of water has been
reached. Program the duration of the impulse between  0.2 and 9 seconds, the
impulse pause between 0.2 and 9 seconds and the number of impulses between 2
and 9.

Menu:

Example of dosing:
as a single impulse

as  multiple  impulses  (4  four-second  impulses and a 10-
second pause:

Dosing impulses are displayed via the asterisk which lights up on the display.

The water meter impulses should not occur quicker than the dosing impulses are processed.

Water meter

Set the number of impulses for the contact water meter in the menu:

Call the recorded quantities in the  “Service” menu, e.g.:

"M"

 

º

 Service 

º

 Operating Info 

º

 WM Desalination: 43 m

3

"M"

 

º

 Service 

º

 Operating Info 

º

 WM Total: 363 m

"M"

 

º

 Service 

º

 Operating Info 

º

 WM Additional Water: 160 m

DOSING

Imp.duration

Litre/Impulse

Impulse pause

No.of impulses

WATER METER

L/Imp. 100.000

Содержание EcoControl DO10

Страница 1: ...EcoControl DO10 Desalination and Dosing Controller Operating Instructions...

Страница 2: ...dosing medium container empty 8 Programming 8 Menu start 8 Menu selection Selection 8 Input 8 End menu 8 Information Menu 8 Programming 8 Enter password 8 Change password 8 Description of functions an...

Страница 3: ...the switching outputs and the total power rating of the plant must not be exceeded The controller should only be used for its specified intended purpose Safety notes Always pay attention to the follo...

Страница 4: ...2 17 General Description View of the unit Mains switch Terminal box Internal view F1 Fuse M0 08A F2 Fuse T4A visible type fuse 20 x 5 F3 Fuse M0 2A...

Страница 5: ...gger functions via the ENTER key F Arrow keys Use these keys to operate the menu drive in the display and to enter values and programming data G M key Call the menu and return to the submenu levels H...

Страница 6: ...ater volumeter remain even during a voltage loss The real time clock is battery buffered and thus keeps on running Confirm the fault display via the Alarm key Error message Des val OPEN You have activ...

Страница 7: ...mally open Volt free relay output max load 240 V AC 4 A 16 17 18 AL EV OUT Output alarm input valve c contact Output AL EV nc normally closed Output AL EV no normally open Volt free relay output max l...

Страница 8: ...4 one second impulses with a 3 second pause should be provided per 50 litres Litre Impulse 50 0 Impulse duration 1 0sec Impulse pause 3 0sec No of impulses 4 Note The impulse ratio in litres impulse s...

Страница 9: ...ination water S Total quantity of additional water S Quantity of evaporation water FC monitoring input desalination valve flow controller Monitors whether the desalination valve is closed and no water...

Страница 10: ...menu option via the ENTER key i e you jump into a submenu Call the next menu option via the DOWN arrow key Scroll through the menu this way Input Inputs are only possible in the BASIC PROGRAM menu an...

Страница 11: ...olume has been reached Desalination Automatic desalination The water meter impulses are added up After reaching the preset quantity of water start volume in litres sum of impulses x basic number of th...

Страница 12: ...tely Dosing You can use the dosing valve or solenoid or motor dosing pumps Select the controller according to the requirements Single impulse For the single impulse The dosing output relay K2 is switc...

Страница 13: ...n active flow controller for flow through Diagram of desalination monitoring Output AL EV draining function Program the function EV to activate the Draining function The input valve is closed and the...

Страница 14: ...he manual function Auto desalination Press the ENTER key to start desalination with the programmed desalinaton time The menu is exited the operating display Desalination appears and the Desalination l...

Страница 15: ...k only continues to run if the unit is switched on Correct if necessary the time and date after a longer period of voltage loss or if the plant has been switched off Anzeige M Service Time Date The di...

Страница 16: ...ut are displayed as on inactive statuses as off e g OUTPUT AV or INPUT FC off on Software status Call the current software status here Draining Start the Draining function via the ENTER key The displa...

Страница 17: ...4 05 Water meter MANUAL IMPULSES Desalination 12 03 02000 l DESAL TIME mm ss 02 30 START VOLUME Desal time Imp duration Litre Impulse Impulse pause No of impulses FCT EMPTY Norm closed Norm open Delay...

Страница 18: ...16 17 Technical appendix Example of a simple circulating coolant Connection example...

Страница 19: ...Degree of protection IP54 Protection class I Conformity EN 50081 1 EN 50082 2 EN 61010 1 Ambient temperature 10 45 C Dimensions EcoControl DO10 W x H x D 175 x 165 x 135 mm Weight approx 0 8 kg We res...

Отзывы: