Instruction for use • Switch unit AGS 80 D
Seite 16 von 29
To 4) The sub-menu „Info“ allows you to view the following system information:
−
System time
−
Next service month
−
Serial number
−
Software versions
To 5) The upper and lower alarm thresholds for ”Flasche Links/cylinder left“, ”Flasche
Rechts/cylinder right“, “Kaltvergaser/liquid gas vaporizer“, ”Mitteldruck/medium pressure“ and
”Netzdruck/mains pressure“ can be changed in this sub-menu.
Use the UP and DOWN keys to select the value to be changed. The entry is displayed in inverse
form when you use the ENTER key and can then be changed by means of the UP and DOWN
keys. Pressing the ENTER key again will inactivate the inversion and save the value. Use EXIT
to leave the sub-menu.
Pressure sensor
Lower threshold
Upper threshold
Steps
0 – 250 bar
10 – 250 bar
10 – 250 bar
5 bar
0 – 20 bar
5 – 20 bar
5 – 20 bar
1 bar
0 – 12,5 bar
3 – 6 bar
3 – 6 bar
0,1 bar
Table 4: Ranges for setting thresholds
To 6) Sub-menu ”Service“
This menu item is used to determine and carry out the basic settings and customer-specific
parameters of the control system.
In order to guarantee trouble-free operation only expert service personnel has access to this menu
item.
Содержание AGS 80 D
Страница 1: ...Instructions for Use Switch Unit AGS 80 D Variant A ...
Страница 24: ...Instruction for use Switch unit AGS 80 D Seite 24 von 29 11 Technical Documentation High pressure reducer ...
Страница 26: ...Instruction for use Switch unit AGS 80 D Seite 26 von 29 ...
Страница 27: ...Instruction for use Switch unit AGS 80 D Seite 27 von 29 ...
Страница 29: ...Instruction for use Switch unit AGS 80 D Seite 29 von 29 ...