VIEW EVENT HISTORY
This latest version of the ENDEAVOUR now incorporates a basic
event logger that records the last 7 "ON" switching events.
example 01 : RELAY 3 ON 15/10/2019 16:30
02 : RELAY 2 ON 15/10/2019 16:50
03 : NIGHT PURGE ON 16/10/2019 04:35
The history can be reset & cleared by pressing the
UP
button from the
1st event which prompts an "erase history message" question ..pressing
ENTER
clears the history.
RELAY PARAMETERS
PROGRAMMING
To set or edit the Relay modes of operation and switching parameters
etc
, Press the fascia
button labeled “
ENTER
” to have the LCD display jump to the 1st menu item in the
menu tree :
“SET CLOCK”
, scroll down through the menu tree with the “
DOWN
” arrow button until
“RELAY
PROGRAMMING”
is displayed. Press the “
ENTER”
button to open this menu. A "
summary
screen
" (not editing screen) is then
be
displayed for Relay 1, the other
3
relay summary
screens can be seen by simply scrolling up or down this sub menu using the “
UP
or
DOWN
”
arrow buttons. To edit the parameters for a particular relay, whilst at its summary screen press
the “
ENTER
” button to display its 1
st
item to edit which is
“
MODE
”
of operation -:
the relays
can be set as
"UNUSED" , "COOL ONLY" (
C
), "HEAT ONLY" (
H
), "HEAT &
COOL" (
B
)
(which is short for acting as BOTH a heating & a cooling mirrored stage), "
CO2"
(
0
)
control or
as an (auxiliary)
TIME SWITCH (2)
relay. If a relay is
not required, to save confusion,
set
it to
“UNUSED” (it’s
associated led will also be disabled).