HE 5731 Operating instructions
33
# 373344, Version 1.5
Operation of the control
7.5. Enable / Disable Precoating
Enable:
Press the TEST key and the UP key simultaneously.
“
PrE
” is displayed alternately with other information.
Disable:
Press the TEST key and the DOWN key simultane-
ously.
After reaching the first cleaning threshold (increased by the precoating), the precoating is
automatically disabled.
.
7.6. Reset Default Settings
Note!
If a password has been assigned, it must be entered during reset. After
the reset, the password is 0. A new password must be assigned. (
see
chapter 6.1 Read out and set
1.
Switch on the device while keeping both keys UP and DOWN
pressed for 5 seconds.
EEP
2.
EEP
is displayed.
cod
3.
When the 5 seconds are up,
cod
is displayed to enter the
password.
4.
Press the ENTER key to start the password entr
5.
After entering and acknowledging the last digit of the pass-
word, the control starts with default parameters (
see 7.2 Pa-
6.
If no password has been assigned, the control starts
automatically after 5 seconds with default parameters (
see