Menu navigation and adjustment values
9
51
9.13.6
Solar
NOTE: At the solar module 5 resp. 6 (only at external solar module) program numbers are available, which
are set up by the service technician. The only differences of the programs are the integration and the number
of tanks (e.g. hot water tank, buffer). The hydraulic schemes of the different modules are described in
appendix 15.2.
Navigation:
→
→
SOLAR
Screen:
By pressing the button:
the „Solar status“ menu will be displayed
the menu for the "settings" will be displayed
the menu for the "Aggregate-
Test“ will be displayed
the „solar yield“ menu will be displayed
Term
Description
Unit
Menu "Status"
Status 1
1
Collector flow
temperature
Indicates the collector flow temperature
°C
Collector back flow
temperature
Indicates the collector backflow temperature
°C
Tank 1 temperature
Indicates the temperature of tank 1
(e.g.: hot water tank, buffer)
°C
Tank 2 temperature
Indicates the temperature of tank 2
(e.g.: hot water tank, buffer) (only visible, if program 3, 4, 5 or 6 is
chosen)
°C
Collector pump
Indicates the status of the collector pump (On/Off)
-
Loading pump
Displays the condition of the backflow pump (On/Off)
-
Menu "Settings"
Settings
1
Pump trigger
Setting up the minimum collector temperature (15-70) to startup the solar
pump
°C
Содержание pelletfire 20/20
Страница 1: ...OPERATING INSTRUCTIONS Log wood pellet heating system pelletfire 20 40 ...
Страница 22: ...8 Temperature manager 22 Figure 8 2 Example temperature manager when time mode without difference ...
Страница 90: ...15 Annex 90 15 ANNEX 15 1 Additional boiler module Hydraulic recommendation 1 ...
Страница 91: ...Annex 15 91 Hydraulic recommendation 2 ...
Страница 92: ...15 Annex 92 15 2 Solar module Program 1 ...
Страница 93: ...Annex 15 93 Program 2 ...
Страница 94: ...15 Annex 94 Program 3 ...
Страница 95: ...Annex 15 95 Program 4 ...
Страница 96: ...15 Annex 96 Program 5 ...
Страница 97: ...Annex 15 97 Program 6 ...
Страница 98: ...16 Notes 98 16 NOTES ...
Страница 99: ...Notes 16 99 ...