Press
“ ”, the programmable temperature is flashing, “▲” or”▼” to set the programmable temperature. Press“ ”, repeat
the above steps to set up the 2
~
4 periods of Monday.
Week
Period NO. 1
Period NO. 2
Period NO. 3
Period NO. 4
Starting Time/
Temperature
Starting Time/
Temperature
Starting Time/
Temperature
Starting Time/
Temperature
Mon
7:00
25
℃
8:00 25
℃
18:00
25
℃
21:00
25
℃
Tue
7:00
25
℃
8:00
25
℃
18:00
25
℃
21:00
25
℃
Wed
7:00
25
℃
8:00
25
℃
18:00
25
℃
21:00
25
℃
Thu
7:00
25
℃
8:00
25
℃
18:00
25
℃
21:00
25
℃
Fri
7:00
25
℃
8:00
25
℃
18:00 25
℃
21:00
25
℃
Sat
7:00
25
℃
8:00
25
℃
18:00
25
℃
21:00
25
℃
Sun
7:00
25
℃
8:00
25
℃
18:00
25
℃
21:00
25
℃
Repeat the above steps to set for TUE, WED, THU, FRI, SAT, SUN.
Keypad Lock Function
Keypad Lock: its keypad would be automatically locked in 30 seconds in case that no one uses the thermostat,
so as to prohibit other persons from operating the thermostat.
Keypad Unlock
:
Press“ ”for 5 seconds to unlock
(
In case that no one uses the thermostat, its keypad would be
automatically locked in 30 seconds
)
.
Low Temperature Protection Function
Turn off: When the room temperature is lower than 5
℃
, the thermostat would automatically turn on the fan and
valve
with “ ” showing, When the room temperature reaches to 7
℃
, the thermostat will automatically close the output.
Low Temperature Protection Setting
Turn off:
press” ” and hold for 3 seconds, it will display “OF” or “ON”, press “▲” or “▼”button to adjust the
parameter
. “OF” indicates low temperature protection invalid, “ON” indicates low temperature protection function valid.
The default is “OF”.
Temperature Adjustment
In case that the user wants the displayed temperature on the thermostat higher or lower than the real
temperature(±5
℃
), the following operations could be taken
:
Turn off: press
“▲” and “▼” at the same time for 3 seconds, it will display “XX
℃
”
(
not displaying the working
model
)
, press
“▲”or “▼” to adjust the temperature value, it will be automatically confirmed after 6 seconds.
Alarm
if the sensor has failure,
the thermostat will close the fan and valve, displaying “E1” or “E2”.
E1
:
Sensor in short circuit alarm
E2
:
Sensor in open circuit alarm
It displays
“HI” when the temperature is higher than 55
℃
, displaying “LO” when the temperature is lower than
0°C