Herrtronic AD Series Installation, Operation and Service Manual
*If the conductivity of your supply
water is less than 100 micromho,
Consult Herrmidifier for specific
circuit board adjustments.
**Your actual cylinder life may be
higher or lower depending on
the exact composition of your water
supply.
Adjustable Set-point
Capacity
•
Range=50-100%
•
Preset at 100%
Low Drain Threshold
•
Range=50-100%
•
Preset; setting varies by unit
Cycle Time
•
Range=60-300
Sec.
•
Preset; setting varies by unit
Faults
Overcurrent
•
120% of Rated Current
•
System
Shutdown
Cylinder Fill
•
Fill valve open for 45 minutes without achieving capacity setpoint
•
System
Shutdown
End of Cylinder Life
•
45 Minutes of operation without achieving capacity setpoint
•
System
Shutdown
Conductivity*
Micromhos
(approx.)
Average Life**
Expectancy – Hrs.
(approx.)
70
2000
100
2000
135
1900
170
1800
255
1300
510
800
765
650
1020
500