7.3
Fault table
Fault
Cause
Remedial action
Safety valve does
not respond
Covers have not been
removed;
Remove covers.
Test pressure too high;
Replace the safety valve.
Back pressure not taken into
account;
Replace the safety valve.
Not liftable
Pressure below 85% of the set
pressure;
Lifting in the range ≥85 % of the set
pressure without aids.
Leak in the
seating
Foreign bodies between cone
and seating, contaminated
medium;
Remove foreign bodies by briefly
lifting / flush the system or replace
the safety valve.
Seating damaged;
Replace the safety valve.
Cone seal damaged;
Replace the safety valve.
Safety valve has chattered;
See "Chattering".
Damage to the
inlet/outlet
Transport damage;
Replace the safety valve.
Wrong connecting thread /
tightening torque too high;
Replace the safety valve.
Impermissible forces such as
bending or torsional forces are
being transmitted;
Install stress-free.
Shock waves
Safety valve not mounted at
the highest point;
Install the safety valve at the
highest point.
water not drained correctly or
at all;
Attach water drain according to
regulations.
Constantly
blowing off
Spring corroded by
impermissible medium and
broken;
Replace the safety valve.
System pressure too high
Replace the safety valve.
Seal damaged;
Replace the safety valve.
Chattering
Pressure drop in the inlet line
>3%;
Reduce resistance through chamfer
or radius in the connecting socket;
choose a larger one if necessary.
Shorter inlet line.
Incorrect safety valve; exchange it.
Seals for inlet and outlet
connector too small or not
installed centrally;
Change conditions.
Safety valves are too powerful;
choose smaller safety valves.
Outlet line too long or diameter
too small;
Use a larger nominal diameter or a
back-pressure-compensating
stainless steel bellows. The max.
height is to be specified by the
manufacturer.
Inlet or outlet connector too
small;
Dimensions must be larger than the
nominal inlet or outlet diameter.
Back pressure higher than 3%;
Use back-pressure-compensating
stainless steel bellows. The max.
height is to be specified by the
manufacturer.
Inadequate
capacity
Safety valves dimensioned
incorrectly for the plant
conditions;
Re-dimension and replace the
safety valve.
Safety valves not being used in
accordance with the applicable
regulations;
Change conditions.