   Model CBC/CBR-103,104,105,106,107

3-5.      PROGRAMMING

dS: 

(defrost system (computation))  dF=digifrost feature;

            Continued

defrost start time based on total compressor running time.
rt=real time; defrost start frequency, based on real time

dI: 

(defrost interval)  defrost frequency in hours, based on the

selection of “dS”

dE: 

(defrost endurance) total (maximum) length of a defrost

 cycle, expressed in minutes. (1...99 range)

dL: 

(display lock)  temperature display is locked during a

 defrost cycle.  (0...31 range)
 “n”=no (readout continues to display the actual tempera-
        ture, even during a defrost cycle
“y”=yes (readout is locked)

dr: 

(display read-out)  select the type of visualization in case of

temperature display lock during defrost (see prameter 

dL

)

“C”=the temperature displayed at the start of a defrost is

   locked and does not change during this cycle

“dF”=during the defrost “dF” is displayed

do:

 (defrost at power on)  selects whether or not, the system

goes through the defrost cycle at start-up (or after power
failure)
“n”=no
“y”=yes

dd: 

(defrost delay at power on)  delay of defrost cycle, in
minutes. (0...99 range)

Error Code “E1”

This is the only error code in these controls.  It indicates a tempera-
ture sensor failure, such as, a shorted sensor, a sensor break, or
absence of sensor.

It can also indicate an under-range in the system temperature (-55).

In case of an over-range in the system temperature, “99” shows first
in the display, followed by “E1”.