Installation instructions

Absolute Shaft Encoder 
RX70TPRX /RX 71TP 
with PROFIBUS-DP

Page 5/8

Introduction

These installation instructions are provided for the connection and starting
procedure of your shaft encoder.

This encoder is EX-tested and licensed. On request, we will be pleased to
send you the respective certificate of conformity PTB00 ATEX 1107

For information concerning software and set parameter please refer to the
Technical Manuals with following item numbers:
2 543 037 — in German
2 543 045 — in English.
You can obtain these manuals by order or by Internet-download from our
homepage www.hengstler.de.
You will get further informations on request.
Additionally available: GSD file ”HENx00B7.GSD” with item number
1 543 062 or by download from our homepage.

This sign marks paragraphs particularly to be observed to assure
proper use and to avoid risks.

Safety and Operating Instructions

• The absolute shaft encoders of the type RX70TP model series are quality 

products manufactured in accordance with established electrical engineering
standards.
The units have been delivered from the factory in perfect conformance to
safety regulations.
To maintain this condition and to ensure trouble-free operation, please ob-
serve the technical specifications of this document.

• Installation and mounting may only be performed by an electrotechnical 

expert!

• The units may only be operated within the limits specified by the technical 

data.

Maximum operating voltages must not be exceeded!

The units are designed complying with DIN EN 61010-part 1, protection class III.
To prevent dangerous structure-borne currents, the equipment has to be run
on safety extra-low voltage (SELV) and must be in an area of equipotential
bonding.
Please use an external fuse for protection (see Electrical Data).

• Fields of application: industrial processes and controls.

Overvoltage at the connecting terminals must be limited to overvoltage-
class-II values.

• Please avoid shocks to the housing – especially to the encoder shaft – and

axial or radial overload to the encoder shaft.

• Maximum accuracy and durability of our shaft encoders are only granted

when using suitable couplings.

• The high-quality EMC-specifications are only valid together with standard-

type cables and plugs. 

When using screened cables, the screen must bro-

adly be connected with ground on both ends. Likewise, the voltage-supply
cables should entirely be screened. If this is not possible you will have to
take appropriate filtering measures.

• Installation environment and wiring are influential on the encoder's EMC:

Thus the installer must secure EMC of the whole facility (device).

• In electrostaticly threatened areas please take care for neat ESD-protection

of plug and connecting cable during installation work.

At the beginning and at the end of each segment, the DP bus must be ter-
minated by an active bus termination!
For trouble-free operation, the voltage supply of both bus terminations
must always be ensured.

• The connecting cable is only suitable for fixed installation (no haulage operating).

The facility installer is responsible for cable selection with consideration of
EX-rules.

The pressure-proofly encapsulated encoder housing must not be opened.

General design

as per EN 60010-1 , protection class III,
contamination level 2, overvoltage class II

Supply voltage (SELV)10 …30 VDC with pole protection
Intrinsic power consumption max.; 230 mA
external fuse

T 0.25 A

EMC

1)

Noise emission as per EN 50081-2
Noise immunity as per EN 50082-2

Interface

RS 485

Protocol

PROFIBUS-DP
with Encoder profile class C2 (can be parameterised)

Baud rate

automatically adjusted in a range
from 9.6 KBit/s up to 12 MBit/s

Device address

adjustable by DIP switches or bus (by DPM2 device

2)

)

Physical resolution

3)

1,024 steps (10 Bit) Singleturn
4,096 steps (12 Bit) Singleturn
8,192 steps (13 Bit) Singleturn
16,384 steps (14 Bit) Singleturn
4,096 steps/4,096 turns (24 Bit) Multiturn
8,192 steps/4,096 turns (25 Bit) Multiturn
16,384 steps/4,096 turns (26 Bit)Multiturn

Linearity

±

1

/

2

LSB (± 1 LSB with resolution13, 14, 25, 26 Bit)

Type of code

Binary

Code sequence

programmable (standard: cw)

Item No. 2 539 042, 3070901HO

Subject to technical modifications and improvements serving the progress of our devices.

Enclosure: EC declaration of compliance  RX 71T No. 2539906

Explosion protection classification

HENGSTLER EXPLOSION-PROOF shaft encoders are classified according to EX II 2 G EEx d
IIC T6/T4 (as per EN 50014 and EN 50018) Cerificate of conformity: PTB00 ATEX 1107

Shaft diameter

10 mm

Shaft load

radial 100 N, axial 40 N

Max. speed 

10,000 RPM (EEx d IIC 

T4

), 6,000 RPM (EEx d IIC 

T6

)

Torque

≤ 

1 Ncm

Moment of inertia

20 gcm

approx.

Protection class 

housing IP 65, bearing IP 64

1)

ambient temperature

-20°C...+60°C EEx d IIC T4

-10°C...+40°C EEx d IIC T6

Storage temperature

–25 … +85 °C

Vibration performance(IEC 68-2-6)100 m/s

2

( 10..60 Hz 1,5mm;60..2000 Hz 100m/s

2

)

Shock resistance (IEC 68-2-27)1,000 m/s

(6 ms) 

Connection

cable axial or radial for fixed installation

Size

∅ 

70 mm

Mounting

clamping flange, bores 3 x M6

Weight

1,400 g approx.

Mechanical data

Electrical data

T6 = Maximum permissible surface temperature  +85 °C 

1)

T4 = Maximum permissible surface tempe130 °C 

2)

1)

EEx d IIC

T6

: max. speed =6,000 RPM and ambient temperature -10..+40 °C

2)

EEx d IIC 

T4

: max. speed =10,000 RPM and ambient temperature -20 ... +60 °C

1)

no standing water allowed at the shaft entrance or at the ball bearing

1)

With compliance with screening indications

2)

Class 2 master

3)

Real code-disc resolution; in addition, the desired resolution can be reduced by programming the encoder

Содержание RX70TPRX /RX 71TP

Страница 1: ...Überspannungen an den Anschlußklemmen müssen auf Werte der Überspan nungskategorie II begrenzt werden Vermeiden Sie die Einwirkung von Schocks auf das Gehäuse vor allem auf die Geberwelle sowie axiale und radiale Überlastungen der Geberwelle Die maximale Genauigkeit und Lebensdauer der Geber wird nur bei Verwen dung einer geeigneten Kupplung garantiert Die guten EMV Werte gelten nur in Verbindung ...

Страница 2: ...glich Deshalb kann die Geräte Adresse nur über den Bus durch ein DPM2 Gerät Klasse 2 Master eingestellt werden Die Geräteadresse darf im Bereich 1 125 eingestellt werden Standardeinstellung bei Auslieferung ab Werk Geräteadresse 32 Anschlußbelegung Nr Signal Beschreibung 1rs B OUT Receive Transmit Data Positive B gr A OUT Receive Transmit Data Negative A 1ge B IN Receive Transmit Data Positive B 1...

Страница 3: ...schritten angegeben Konfiguration DDLM_Chk_Cfg Der DP Master legt mit dieser Routine die Anzahl der Bytes für den Datenaustausch fest Octet Bit Daten Funktion 1 7 0 D1h Eingangsdaten 2 Worte Standardkonfiguration 32 Bit Positionswert class 1 F1h Eingangsdaten 2 Worte Ausgangsdaten Standardkonfiguration 32 Bit Positionswert Preset class 2 D0h Eingangsdaten 1 Wort Optionale Konfiguration 16 Bit Posi...

Страница 4: ...etriebnahme durch Standard Profibus DP Tools mit der GSD Datei hier am Beispiel COM PROFIBUS Wählen Sie unter Sollkonfiguration die gewünschte Konfiguration siehe Tabelle Seite 3 Im Fenster Konfigurieren tragen Sie die die gewünschten Daten Kommentar E Adresse A Adresse etc ein Im Fenster Parametrieren können Sie nun die Geberparameter siehe Bild durch Anklicken des jeweiligen Feldes unter Spalte ...

Страница 5: ...cility device In electrostaticly threatened areas please take care for neat ESD protection of plug and connecting cable during installation work At the beginning and at the end of each segment the DP bus must be ter minated by an active bus termination For trouble free operation the voltage supply of both bus terminations must always be ensured The connecting cable is only suitable for fixed insta...

Страница 6: ...ddress via the bus The device address may be set in a range from 1 up to 125 Standard setting delivered from factory D De ev vi ic ce e a ad dd dr re es ss s 3 32 2 Connection diagram No Signal Description 1rs B OUT Receive Transmit Data Positive B gr A OUT Receive Transmit Data Negative A 1ge B IN Receive Transmit Data Positive B 1gn A IN Receive Transmit Data Negative A br VCC1 5 V Signal output...

Страница 7: ...P master defines the number of bytes for data exchange Octet Bit Data Function 1 7 0 D1h 2 words of input data standard configuration 32 bit position value class 1 F1h 2 words of input data output data standard configuration 32 bit position value Preset class 2 D0h 1 word of input data optional configuration 16 bit position value class 1 F0h 1 word of input data output data optional configuration ...

Страница 8: ...he Preset Configuration list choose the desired configuration see table on page 3 In the Configure window complete the desired entries Remarks I Adress O Address Now in the Parameterize window you may modify the encoder parameters correspondingly see figure above Click on the respective field from the Value column and activate the Select button Parameter indications Sampling rate velocity only By ...

Отзывы: