BPPI 6.19

 

f)  Perform the test. With the BPK Probe™ brushes pressed against the motor shaft, press and 

hold the trigger switch throughout the test. As the test starts, the Helwig Carbon logo will 

show (Figure 8). 

g)  Next, a SAMPLING SHAFT VOLTAGE message will appear (Figure 9). Continue to hold the 

trigger switch with the tip of the probe against the motor shaft. When complete, the screen 

will show a real-time test result (Figure 10).  

h)  Carefully remove the probe from the motor shaft, note the results, and release the trigger. 

Remove the ground clamp and replace the protective tip cover. The test is complete. 

i)  The shaft voltage test can be repeated with and without 

engaging the embedded grounding brush. To enable the 

grounding brush, press the rocker switch on the face of the 

probe handle. The embedded grounding brush is enabled 

when the green LED on the switch is lit. Testing with the 

grounding switch enabled shows the effectiveness of the 

Helwig grounding solution (Figure 11). 

 

 

Figure 8: As the test starts, the Helwig 

Carbon logo will show. 

Figure 9: A SAMPLING SHAFT 

VOLTAGE message will appear. 

Figure 10: Test results for unprotected 

motor. 

Figure 11: Test results with 

grounding switch enabled. 

Содержание BPK Probe

Страница 1: ...Page 1 of 8 BPPI 6 19 BPK Probe Shaft Voltage Detection Device Operating Guide...

Страница 2: ...wered or controlled machines the equipment as well as the electrical system itself must be properly grounded High pressure systems too need careful inspection and maintenance to prevent possible failu...

Страница 3: ...motor shaft voltage It also demonstrates the effectiveness of a bearing protection kit BPK if a BPK is installed Components BPK Probe Assembly Features 4 Extension Tube Spare Tips BNC Cable Ground Wi...

Страница 4: ...s oils and contamination b Using the rubber flap side of the Probe Preparation Tool Figure 3 identify a contact area on the shaft for measurements c Verify the contact area is clean and not in line wi...

Страница 5: ...ured verify the rocker switch is off LED not lit This disables the embedded grounding brush b Remove the protective sensor tip cover and keep nearby c On a suitable and properly prepared surface caref...

Страница 6: ...lts and release the trigger Remove the ground clamp and replace the protective tip cover The test is complete i The shaft voltage test can be repeated with and without engaging the embedded grounding...

Страница 7: ...ow to operate the probe you will get a flashing LOW BATTERY message Figure 13 The probe will not allow testing until the battery is changed c To change the battery loosen the retaining screw on the bo...

Страница 8: ...E PREPARATION TOOL 2 BKCT2392A 5 ND GROUND CLAMP 3 501 1377 ND GROUND WIRE 4 ACX1813 ND BNC CABLE 5 PTE 04 PROBE TIP EXTENSION 4 6 PTE 06 PROBE TIP EXTENSION 6 7 PTE 12 PROBE TIP EXTENSION 12 8 PT 01...

Отзывы: