background image

Helvar Ltd 

Hawley Mill 

Hawley Road 

DARTFORD 

DA2 7SY 

UNITED KINGDOM 

www.helvar.com

4

Doc. 7860342, issue 2, 2015-12-15

Helvar

 | Data is subject to change without notice.

Time Setup

Set the time appropriately for the usage of the area. For example, some possible settings could be:
•  Offices with workers regularly walking: 

20 min

•  Offices with mainly desk-based workers:  40 min
•  Corridors: 

5 min

•  Washrooms with total coverage: 

10 min

•  Washrooms with entry coverage only: 

40 min

•  2D fittings: 

Not less than 20 min, due to potential lamp failure. If in doubt, contact your lamp

 

manufacturer.

Technical Data

Back mounting plate

Dimensions (mm)

Electrical data

External power: 

Terminal block 

Wire section: 0.5 mm² – 2.5 mm² 

solid or stranded

Cable rating:

All cables must be mains rated.

Mains supply:

230 VAC, 50 Hz

Loads

6 A resistive (e.g. heater) 

4 A incandescent 

3 A fluorescent ballast / LED 

driver 

1 A inductive (e.g. fan/motor) 

Mains LED lamps: Equivalent to 

1000 W halogen light output 

Min. load: 2 W resistive, suitable 

for most energy saving lamps, 

LEDs and emergency fittings.

External 

protection:

6 A maximum (MCB or fuse)

Illuminance:

10 lx to 1000 lx, or photocell 

inactive.

Sensors

Presence detector:

PIR (Passive InfraRed)

Detection range

360° with up to 7 m diameter 

when mounted at a 2.8 m ceiling 

height

Time:

10 s to 40 min

Mechanical data
Mounting hole 

diameter:

50 mm

Diameter:

86 mm

Material (casing):

Flame-retardant polycarbonate

Finish / Colour:

Matt / White RAL9003

Weight:

102 g

IP code:

IP20

Operating conditions

Ambient 

temperature:

+10 °C to +35 °C 

Note: The temperature difference 

between the detection target and 

the background must be at least 

4 °C.

Relative humidity:

Max. 90 %, noncondensing

Storage 

temperature:

–10 °C to +70 °C

Conformity and standards

EMC emission:

EN60669-2-1:2004 inc A12:2010

EMC immunity:

EN60669-2-1:2004 inc A12:2010

Safety:

EN60669-2-1:2004 inc A12:2010

Environment:

Complies with WEEE and RoHS 

directives.

Version information

Hardware version:

Rev. 1

Sensor head

16.1

18.4
60.3

 90.5

 86

45.5

18.4 50

Отзывы: