HELVAR Digidim 458M Series Скачать руководство пользователя страница 6

Helvar 458 MX Chassis: Installation Guide

Doc. 7860213, issue 07 

2015-01-14

11 

Helvar

 | Data is subject to change without notice.

www.helvar.com   

10 

Dimensions: Case (mm)

Technical Data

178

362

37

137

317

355

273

178

753

37

705

273

458M1

458M2

458M3

Connections

Mains supply:

230 VAC / 400 VAC

Supply protection:

External MCB or fuse 

458M1, 458M2, 458M3: 63 A (max.) 

for each position 

Single phase use: 125 A (max.) 

Note: Supplying multiple blocks of 

MCBs on the same phase requires 

this limit because of the neutral 

connection. 

Rated ≤ 17 kA to meet 

EN 61439-2

Load protection:

MCB type C 10 kA. Rating as 

specified for individual units.

SDIM cable loom:

An SDIM cable loom is attached to 

the DIN-rail inside the chassis. 

This can be connected to the SDIM 

terminals of the module(s), to 

enable connection of the module(s) 

to a Helvar Imagine system.

Installation

Mounting:

Vertically wall mounted: 4.5 mm 

mounting holes. 

Use No. 8 or No. 10 screws with 

head diameter of 6 mm to 9 mm.

Mechanical Data

Dimensions:

See diagrams.

Weight:

458MI:

5.9 kg (458M1 including 9 MCBs)

458M2:

12.2 kg (458M2 including 18 MCBs)

458M3:

18 kg (458M3 including 27 MCBs)

Operating Conditions

Ambient temperature:

0 °C to +40 °C 

Relative humidity:

Max. 90 %, noncondensing

Storage temperature:

–10 °C to +70 °C

Conformity and Standards

Safety:

EN 61439-2

Environment:

Complies with WEEE and RoHS 

directives

Connection

Cable type (Cu)

Strip length

Mains supply: 458M1

Up to 16 mm²

16 mm – 17 mm (N); 12-13 (E)

Mains supply: 458M2

6 mm² – 35 mm²

12 mm – 14 mm (N), 17 (E)

Mains supply: 458M3

6 mm² – 35 mm²

12 mm – 14 mm (N), 17 (E)

Channel outputs:

Solid core: 0.25 mm² – 4 mm²; 

Stranded: 0.25 mm² to 2.5 mm²

10 mm – 12 mm

SDIM / DMX

Low-loss 300 V RS485 type;
Multistranded, twisted and shielded;
3- or 4-core plus screen;

Max. length: 1000 m

0.22 mm² – 1.5 mm²
Recommended: two twisted 

pairs (overall screened), 

e.g. Belden 8102 CM. 

Cable Requirements