Technical Data

Connections

External power / DALI:

Removable connector block. 

Wire size: 0.5 mm² – 1.5 mm² 

solid or stranded.

Cable rating:

All cables must be mains 

rated. 

Max. length: 300 m @ 1.5 mm²

Power

DALI supply input:

13 V to 22.5 V

DALI consumption:

15 mA

Sensors

Presence detector:

PIR: Passive infrared 

presence detector

Infrared receiver:

For remote control 

commands. 

Note: Adjust sensitivity using 

Designer or Toolbox (not by 

remote control unit).

Mechanical data

Mounting hole 

diameter:

68 mm

Bezel diameter:

76 mm

Material (casing):

Flame-retardant ABS

Finish / Colour:

Matt / White RAL 9003

Weight:

82 g

IP code:

IP40

Operating conditions

Ambient temperature:

0 °C to +35 °C

Relative humidity:

Max. 90 %, noncondensing

Storage temperature:

–10 °C to +70 °C

Conformity and standards

EMC emission:

EN 61000–6–1

EMC immunity:

EN 61000–6–3

Safety:

EN 60730–1

Environment:

Complies with WEEE and 

RoHS directives.