background image

2

Helvar 314 Tilting Microwave Detector: Installation Guide

Surface back box SBB-B

93mm

82mm

85mm

60mm

51mm

Fixing screw

1.

4.

•  Position the detector so that the occupants of the room are normally inside the detection zone. 

•  Do not install the detector within 1 m of any lighting, forced air heating, or ventilation equipment.

•  Do not fix the detector to an unstable or vibrating surface.

•  Install the unit as far away as possible from the surface of metal objects.

•  The detection pattern illustrated (see ‘Detection Pattern’ on page 1) is based on a mounting height of 2.8 m. A lower 

mounting height will decrease the overall size of the detection zone.

Prerequisites

Installation

Connection, Fitting and Set Up

Connect the DALI 

terminal blocks. 

If required, connect the 

external power cable.

External Power Supply (Optional)

The table below shows the various 12 V to 24 V external 

power supply units that can be used and the sensor 

hardware revision needed for each of them. 

EPS

Current 

limited

Link from 

DA– to EPS–

Sensor hardware 

revision

Helvar 401

Yes

No

Any

Helvar 402

Yes

Yes

Any

Helvar 403

Yes

No

Any

Helvar 

LL1x30-E-CV24 Slow

No

4 or later

Generic 

12 V to 24 V

No

No*

4 or later

Note

:

 In some cases the generic EPS output is referenced to earth.

With some models, you must make a wire 

link between the DALI negative terminal 

and the negative terminal of the external 

power supply, as shown in the figure.

+

-

+

-

2.

Attach the cable clamp.

Insert the detector into the 

cutout. Take special care when 

bending the springs back

3.

Ø 78 mm

Ensure the fitted unit sits flush 

to the ceiling.

4.

With the circuit switched on the 

LED in the sensor will flash red 

for 30 seconds.

When the detector is activated the relating light load will 

illuminate and remain on for a defaulted time of 20 minutes if 

there is no other movement detected.

C

heck the DALI network connection by selecting the 

Identify

 function 

in Designer or Toolbox

Adjustments to the detector such as sensitivity, On / Off transitions 

and illumination periods can be managed using Designer or Toolbox.

Note:

  Maximum sensitivity makes the detector unit 

extremely sensitive

 

to movement and may detect through glass, thin walls or partitions. If this 

causes a problem, reduce the sensitivity.

When using Designer, connect the PC to the lighting network via a 

Helvar router.

When using Toolbox, connect the PC to the lighting network via a 

Helvar serial or USB interface. 

For information about Designer and Toolbox, visit www.helvar.com.

51mm

82mm

85mm

93mm

60mm

Отзывы: