Helmholz FLEXtra FO 650 Скачать руководство пользователя страница 6

Note

We have checked the content of this Brief instruction for conformity with the hardware and software described. Nevertheless, because deviations 
cannot be ruled out, we cannot accept any liability for complete conformity. The information in this Brief instruction is regularly updated. When 
using purchased products, please heed the latest version of the Brief instruction, which can be viewed in the Internet at  
www.helmholz.com, from where it can also be downloaded.  
Our customers are important to us. We are always glad to receive suggestions for improvement and ideas.
1) BFOC stands for Bajonett Fiber Optic Connector. This type of connector is function compatible with ST connectors.
  ST is registered trademark of company AT&T.
2) PCF stands for Polymer Cladded Fiber and is equivalent to HCS

HCS is a brand of Ensign-Bickford Optics Company.

3) The Versatile Link connector is function compatible with HP-Simplex/Duplex connectors.

Legend

  LED flashes slowly

  LED ON

  LED flashes quickly

  LED OFF

Note: 

if no baud rate is detected, the FLEXtra® FO restarts every 8 seconds. The restart takes approx. 2 seconds. 

FLEXtra® FO 2: DIP switch 5 is for future features and is currently not used.
FLEXtra® FO 5: DIP switch 8 is for future features and is currently not used.

LED

DIP switch

PWR

DP 1-6

-ON- 

-ERR- 

-ON- 

1-3 (FO-2) 
1-6 (FO-5)

deactivated 
4 (FO-2) 
7 (FO-5)

Baud rate is detected, the FLEXtra® FO  
is restarted

ON

ON

Automatic restart e.g.  
in the case of signal loss

ON

ON

FLEXtra® FO ready for operation,  
baud rate detected

ON

ON

Segment switched off

OFF

ON

Repeat function deactivated  
for all segments

ON

OFF

Repeat function deactivated for all  
se individual segments

OFF

OFF

Invalid telegrams are received

ON

ON

Port X1: there is a short circuit
Port X2–X5: there is a continuous light 

signal (no data is being received)

ON

ON

Data is being received

ON

ON

LED description

Brief instruction FLEXtra® FO 650

Brief instruction FLEXtra® FO 650

Brief instruction FLEXtra® FO 650

Technical Data FLEXtra® FO 650-2

Dimensions in mm (D x W x H)

35 x 70 x 72

Weight

approx. 125 g

Power supply

• Voltage
• Electrical isolation
• Current consumption
    ∙ incl. 5V-consumer load
    ∙ incl. 24V-consumer load

+18 ... 30 V DC
500 V

max. 200 mA
max. 400 mA

Technical Data FLEXtra® FO 650-5

Dimensions in mm (D x W x H)

35 x 137 x 72

Weight

ca. 250 g

Power supply

• Voltage
• Electrical isolation
• Current consumption
    ∙ incl. 5V-consumer load
    ∙ incl. 24V-consumer load

+18 ... 30 V DC
500 V

max. 400 mA
max. 600 mA

Technical Data both FLEXtra® FO

Output voltage port X1

• Voltage 1
• Voltage 2

5 V, max. 150 mA
+18 ... 30 V DC, max. 200 mA 

(like supply voltage)

Permitted ambient conditions

• Ambient temperature in operation
• Transport and storage temperature

0°C ... +60°C
-25°C ... +75°C

PROFIBUS interface

Transmission rate

9.6 | 19.2 | 45.45 | 93.75 | 187.5 | 500 Kbps
1.5 | 3 | 6 and 12 Mbps automatic detection

Protocol PROFIBUS DP

according to EN 61 158-2:2011-09

Connection socket

Port X1
Port X2–X5 

SUB-D 9-pin
BFOC

1) 

resp. ST, SMA, Versatile Link

3) 

resp. HP

Special features

Quality assurance according to ISO 9001:2008

Maintenance

maintenance-free, no battery

Optical interface

Wavelength

650 nm

Numerical aperture transmit diode

0.50

Launchable optical output power /  
receiver sensitivity

• POF 980/1000 µm
• PCF

2) 

resp. HCS, 200/230 µm

-7.5 dBm/-20 dBm
-18 dBm/-22 dBm

Over modulation limit receiver

-3 dBm

Bridgeable range

• POF 980/1000 µm (160 dB/km)
• PCF

2) 

resp. HCS, 200/230 µm (10 dB/km)

up to 65 m
up to 250 m

POF-LWL Assembling

A) Cutting the fibre

Slide the fibre into an opening of the cutting tool and 

press the blade down.

Note: 

each opening of the cutting tool may only be used 

for one cut of a cable.

B) Removing the Fibre Cladding

The length of fibre cladding to be removed is depen

-

dent on the type of fibre.

Versatile Link

3)

 resp. HP: approx. 3 mm

SMA: 

approx. 6 mm

BFOC

1)

 resp. ST

approx. 11 mm

Note: 

Only use the specially designed tool (not a copper 

cable stripper) as otherwise the cladding of the cable can 
be damaged leading to higher losses in the connector and 
thereby to reduced range of the cable.

C) Connecting the connector to the fibre 

BFOC

1)

 resp. ST or SMA connector:

Slide the connector over the fibre and screw the 

 

connector housing on with the lock nut. 

Versatile Link

3)

 resp. HP connector:

Slide the connector onto the fibre and press the hou

-

sing sides together until they lock.

Note: 

When attaching the connectors, make sure that the 

fiber ends flush with the connector at the front. 
The transmit or receive diode may be damaged if the fiber 
protrudes. 
Fixing the fiber too far inward can result in increased  
attenuation, shortening the transmission range of the 
system.

SMA connector

BFOC

1)

 resp. ST connector

Versatile Link

3)

 resp. HP connector

Helmholz GmbH & Co. KG

 | Hannberger Weg 2 | 91091 Großenseebach | Germany 

Phone +49 9135 7380-0 | Fax +49 9135 7380-110 | [email protected] | www.helmholz.com