5.5.2
29-bit protocol
Byte
Content Transmit Object
0
Len + RTR
1
HighByte HighWord CAN identifier
2
LowByte HighWord CAN identifier
3
HighByte LowWord CAN identifier
4
LowByte LowWord CAN identifier
5
Data byte 1
6
Data byte 2
7
Data byte 3
8
Data byte 4
9
Data byte 5
10
Data byte 6
11
Data byte 7
12
Data byte 8
The entire CAN message header is stored in the first 5 bytes (0-4).
Byte 0
15 14 13 12 11 10 9 8
Data length
RTR
unused
Byte 1
Byte 2
15
14 8 12
11
10 9 8 7 6 5 4 3 2 1 0
unused
High Word CAN identifier (13 bits)
Byte 3
Byte 4
15
14 8 12
11
10 9 8 7 6 5 4 3 2 1 0
Low Word CAN identifier (16 bits)
Transmission of the message is initiated by inverting bit 0 in byte
0 of the
HANDSHK_OUT
area.
The Transmit Object can be transmitted via the device parameters
of the DP/CAN coupler cyclically by means of a timer.
Cyclic transmission via the timer is triggered by inverting the bit
0 in byte 0 of the
HANDSHK_OUT
area.
A change of transmit data is activated on cyclic transmission only
by inversion of bit 0 in byte 0 of the
HANDSHK_OUT
area.
5.6
PLC diagnostics
SFC 13 – “DPNRM_DG” can be used to fetch the diagnostic data
from a DP slave.
Parameter
Direction
Type
Example
REQ
IN
BOOL
TRUE
LADDR
IN
WORD
W#16#3FE
RET_VAL
OUT
INT ;
MW 100
RECORD
OUT
ANY
P#DB13.DBX0.0 byte 10
BUSY
OUT
BOOL
M 7.0
DP/CAN Coupler
25