SR100HL Series - 100 W Power Supply/Float Charger for Lead Acid Batteries 

7. TECHNICAL SPECIFICATIONS  

 

Output power 

100W (0-50°C ) 

Input Voltage 

180V - 264VAC 45-65Hz 

Output Voltages  

13.8V, 24, 30V, 36V, 48 VDC  
Other voltages by request 

Voltage Adj. Range  

85% - 105% of Vout 

Frequency 

45-65Hz  

Overcurrent protection 

Constant current limit under overload and short circuit conditions 

Isolation 

Input – earth – 2.5KVdc 
Output – earth - 500Vdc 

Efficiency 

> 85% 

Inrush Current 

< 30A , 1.8ms 

Operating temperature 

-20  to 50 °C ambient at full load 

Humidity 

0 - 95% relative humidity non - condensing 

Cooling 

Natural convection 

LED Indication 

Green: DC OK 

Green: Power OK 

Alarms Relay  

Form C contacts changeover, rated 30VDC,2A/110VDC,0.3A/125VAC,0.5A 

DC Hight () 

POWER  (main fails, PSU fail) 

DC Low  () 

Line Regulation 

<0.04% over input range 

Load Regulation 

<0.5% open circuit to 100% load 

Noise 

<0.3% 

Transient response 

200mV over/undershoot, 
Load step 20-100%, 400us settling time 

Hold-up time 

15-20 ms (nom-max. Vin) without battery 

AC input connector 

IEC60320— C13 10A input socket (similar to PCs etc) 

DC Connections 

Plug-in style socket & mating screw terminal block: (max. wire 2.5mm² / way) 

Alarm connections 

Plug in screw terminal block 

Enclosure 

Zinc plated & powder coated steel 

Dimensions 

147W x 177D x 62H (±mm) 

Weight 

0.95 Kg 

EMC  

To CISPR 22 / EN55022 class A  

Safety 

To IEC950  / EN60950 / AS/NZS3260 

9. STANDARDS 

8. PHYSICAL 

Содержание SR100HL

Страница 1: ...L FEATURES STANDARD FEATURES 3 Relay Alarms Form C Float Charger Lead Acid Batteries Temperature Sensor on 1 7m lead with adhesive pad 4mV C cell 10 Comms RS232 RS485 Modbus SNMP Webpages Customizable...

Страница 2: ...2 www heliosps com...

Страница 3: ...WORLD ENGINEERING EXPERIENCE Table of Contents 1 SAFETY 4 2 INTRODUCTION 5 3 FRONT PANEL LAYOUT 5 4 FG Frame Ground 5 5 N 1 REDUNDANCY 6 6 CONNECTION NOTES 6 7 TECHNICAL SPECIFICATIONS 7 8 PHYSICAL 8...

Страница 4: ...es if subjected to high ambient temperatures Water Dust Every effort must be made in the installation to minimise the risk of ingress of water or dust Water will almost always cause instant failure Th...

Страница 5: ...n upon mains failure PSU fails DC Low DC Output Low or Battery voltage low if used as a charger 4 DC CONNECTIONS 5 LED indications Code Mimics alarm conditions above 6 COOMS PORT RS232 ASCII RS485 ASC...

Страница 6: ...ith or without diodes It is essential that the wiring from each unit to the load is kept identical for equal power sharing particularly when diodes are not used 6 CONNECTION NOTES Two outputs connecte...

Страница 7: ...Natural convection LED Indication Green DC OK Green Power OK Alarms Relay Form C contacts changeover rated 30VDC 2A 110VDC 0 3A 125VAC 0 5A DC Hight POWER main fails PSU fail DC Low Line Regulation 0...

Страница 8: ...lios Power Solutions warrants this product for 24 months from date of shipment against material and workmanship defects Liabil ity under this warranty is limited to the replacement or repair of the de...

Отзывы: