Helios SA-3 10 Скачать руководство пользователя страница 10

Three-Step Switch SU/SA

Operating Instructions

3

     EN    

2.0 Functions

Three different setpoint settings can be issued via the three-step switch. Each step 
(S1-S3) is freely adjustable via a separate potentiometer from (...

see table below

) Volts 

(with a Phillips type screwdriver, Ø 3 mm). 
The connection of a weekly timer (WSUP, WSUP-S, accessories) for switching from 
3-step daytime mode to e.g. night mode is also possible. The night/reduction mode is 
freely adjustable via an additional potentiometer (A1) from 0 to 10 V DC.

Only EC fans or frequency inverters, which provide at least 1.5 mA with 10 V power 
supply (controller internal consumption), may be connected.

 

Total current = Internal consumption (controller) + fan load current

  

(load current depends on load of 0-10 V fan input)

All three potentiometers S1, S2 and S3 are set to left stop when delivered. 
The potentiometers must be adjusted to local requirements.

 

2.1  Switching step adjustment range
 

The Three-Step Switch SU / SA has 4 potentiometers:

CHAPTER 2

 

FUNCTIONS 

ATTENTION

 

m

NOTE!

 

   

ò

ù

ò

 

Slide switch

ù 

Scale 

Step S1-S3 

 

Potentiometers:

ò 

Step S1

ù 

Step S2

  

ä 

Step S3

ë 

“A1”

ö 

“S”    

(Meas. point)

ü 

“A”    

(Meas. point)

Å 

“GND”  

(Earth/Ground)

TIP: Voltage measurement:

The output voltage of the supply 

air fan in the set operating mode 

can be measured via 

GND

 and

 S

.

ò

ù

ä

ë

ö

Å

ü

Potentiometer 
adjustment, 

ò

 to 

ë

Fig.1

GND / 1 2 3

Bridge to terminal 2/3  

factory setting,  

see SS-1022)

RJ12

Control line 

Designation 

Scale Designation 

 Adjust. range

S1

Step 1 of supply air fan

0 to 10.0 V

S2

Step 2 of supply air fan

0 to 10.0 V

S3

Step 3 of supply air fan

0 to 10.0 V

A1

Step for WSUP  
or night mode

0 to 10.0 V

GND

Earth/Ground

-

S

Voltage Slide switch

Measurem. point

A

Voltage External command Measurem. point

Содержание SA-3 10

Страница 1: ...is tages 10 V 0 10 V SU 3 10 SA 3 10 mit zus tzlichem Anschluss f r Wochenzeitschaltuhr with additional connection for weekly timer avec raccordement suppl mentaire pour minuterie hebdomadaire Helios...

Страница 2: ...DEUTSCH...

Страница 3: ...stufen Schalter SU 3 10 oder SA 3 10 f r Unterputz bzw Aufputzmontage inkl Anschlusskabel Die Sendung ist sofort bei Anlieferung auf Besch digungen und Typenrichtigkeit zu pr fen Falls Sch den vorlieg...

Страница 4: ...V Eingangs des Ventilators Alle drei Potentiometer S1 S2 und S3 sind im Lieferzustand auf Linksanschlag gestellt Die Potentiometer sind auf die rtlichen Erfordernisse einzustellen 2 1 Einstellbereich...

Страница 5: ...sorgung Eingang 10 V DC Ri 12 5 kOhm Sicherheitskleinspannung Eigenverbrauch 1 5 mA Steuerausgang 0 bis 10 V DC wahlweise ber Schalter oder externe Umschaltung Schutzart IP30 eingebaut Schutzklasse II...

Страница 6: ...S3 RJ12 Buchse 1 2 3 1 6 10 V GND 0 V 0 10 V 1 2 3 1 6 Schalterbetrieb Schalterbetrieb mit Nachtabsenkung 230V SS 1022 Nr 85264 001 25 02 16 optional Aus 0 V WSUP S Art Nr 9577 S1 S2 S3 Adapter RJ12...

Страница 7: ...Dreistufen Schalter SU SA Bedienungsanleitung 6 Notizen DE...

Страница 8: ...ENGLISH...

Страница 9: ...e regulations and CE guidelines at its date of manufacture 1 4 Receipt The delivery contains the Three Step Switch SU 3 10 or SA 3 10 for flush mounting or surface mounting incl connection cable Pleas...

Страница 10: ...ad of 0 10 V fan input All three potentiometers S1 S2 and S3 are set to left stop when delivered The potentiometers must be adjusted to local requirements 2 1 Switching step adjustment range The Three...

Страница 11: ...10 For flush mounting installation in deep FM box D 65 mm Power supply Input 10 V DC Ri 12 5 kOhm safety extra low voltage Internal consumption 1 5 mA Control output 0 to 10 V DC optional via switch o...

Страница 12: ...i S1 S3 RJ12 Buchse 1 2 3 1 6 10 V GND 0 V 0 10 V 1 2 3 1 6 Schalterbetrieb Schalterbetrieb mit Nachtabsenkung 230V SS 1022 Nr 85264 001 25 02 16 optional Aus 0 V WSUP S Art Nr 9577 S1 S2 S3 Adapter R...

Страница 13: ...Three Step Switch SU SA Operating Instructions 6 Notes EN...

Страница 14: ...FRAN AIS...

Страница 15: ...ption v rifier l tat et la conformit du mat riel command En cas d avaries des r serves doivent tre port es sur le bordereau du transporteur Elles doivent tre pr cises significatives compl tes et confi...

Страница 16: ...de la charge de l entr e 0 10 V du ventilateur Les trois potentiom tres S1 S2 et S3 sont fournis tourn s vers la gauche Les potentiom tres doivent tre r gl s en fonction des besoins sur place 2 1 Pla...

Страница 17: ...mm Entr e d alimentation 10 V DC Ri 12 5 kOhm basse tension de s curit Consommation propre 1 5 mA Sortie de commande 0 10 V DC au choix via l interrupteur ou commutation externe Degr de protection IP...

Страница 18: ...oti S1 S3 RJ12 Buchse 1 2 3 1 6 10 V GND 0 V 0 10 V 1 2 3 1 6 Schalterbetrieb Schalterbetrieb mit Nachtabsenkung 230V SS 1022 Nr 85264 001 25 02 16 optional Aus 0 V WSUP S Art Nr 9577 S1 S2 S3 Adapter...

Страница 19: ...Interrupteur trois tages SU SA Mode d emploi 6 Notes FR...

Страница 20: ...en AG Tannstrasse 4 8112 Otelfingen GB HELIOS Ventilation Systems Ltd 5 Crown Gate Wyncolls Road Severalls Industrial Park A HELIOS Ventilatoren Postfach 854 Siemensstra e 15 6023 Innsbruck Colchester...

Отзывы: