230V models: 

There is no connection made inside the YK-PSW5KVA/E Inverter 

from either the line or neutral conductor to the safety ground. 
 

Ground Fault Circuit Interrupters (GFCI

S): 

Installations in Recreational Vehicles (for North American approvals) will require GFCI 
protection of all branch circuit connected to the AC output of the hardwire terminal equipped 
inverter. In addition, electrical codes require GFCI protection of certain receptacles in 
residential installations. While the pure sine wave output of the inverter is equivalent to the 
waveform provided by utilities, compliance with UL standards requires us to test and 
recommend specific GFCI. Our company has tested the following GFCI-protected 20A 
receptacles and found that they functioned properly when connected to the output of the 
inverter. 
 

 

 

WARNING! 

Do  not  operate  the  power  inverter  without  connecting  it  to 
Ground. 
Electrical shock hazard may result. 

 

 

   

 

2-6  Marking DC Wiring Connections: 

Follow  this  procedure  to  connect  the  battery  cables  to  the  DC  input  terminals  on  the 
Inverter. Your cables should be as short as possible (ideally, less than 10 feet / 3 meters) 
and large enough to handle the required Current in accordance with the electrical codes or 
regulations applicable to your installation.   
 
Cables that are not an adequate gauge (too narrow) or are too long will cause decreased 
inverter  performance  such  as  poor  surge  capability  and  frequent  low  input  voltage 
warnings and shutdowns.   
 
  These low input voltage warnings are due to DC voltage drop across the cables from the 
inverter to the batteries. 
 
  The longer and narrower these cables, the greater the voltage drop. 

 

 

WARNING! 

The installation of a fuse must be on positive cable. 
Failure to place a fuse on 

cables running between the inverter 

and battery may cause damage to the inverter and will void 
warranty. 

Содержание RM-PSW 1105KVA

Страница 1: ...0 PSW2205KVA E 2U x 19 rack mount 50 PSW5KVA Series www heliosps com Email New Zealand sales heliosps co nz Australia sales heliosps com au Asia Middle East sales heliosps asia REV 22 05 2020 50 PSW24...

Страница 2: ...n 7 2 4 Quick hook up and testing 8 2 5 AC safety grounding 9 2 6 Making DC wiring connections 10 2 7 Inverter operation 11 2 8 Cooling fan working code 13 3 Maintenance 13 4 Troubleshooting guide 14...

Страница 3: ...Application l Power tools circular saws drills grinders sanders buffers weed and hedge trimmers air compressors l Office equipment computers printers monitors facsimile machines scanner l Household it...

Страница 4: ...0VDC 20VDC 42VDC 90VDC 180VDC No load Current Draw 1 64A 0 82A 0 42A 0 24A 1 30A 0 68A 0 35A 0 18A Output Voltage Adjustment 100 120V Tune VR 200 240V Tune VR Frequency 50 60Hz 0 05 Switch Selectable...

Страница 5: ...4 1 3 Mechanical Drawings...

Страница 6: ...ons in this manual before installing and using this model 2 1 Front Panel Operation 2 1 1 Front view 2 1 2 ON OFF switch Please leave in the OFF position during installation 2 1 3 Function Key When se...

Страница 7: ...egative Reverse polarity connection will blow internal fuse and may damage inverter permanently 2 2 4 RS 232 Connect to computer to remote control working status Alarm relay operation Voltage free con...

Страница 8: ...afety hazard WARNING Shock Hazard Before proceeding further carefully check the inverter is NOT connected to any batteries and that all wiring is disconnected from any electrical sources Do not connec...

Страница 9: ...nd could result in a potential hazard 2 3 3 Safe Do not install in a battery compartment or other areas where flammable fumes may exist such as fuel storage areas or engine compartments 2 3 4 Ventilat...

Страница 10: ...ompletely 2 4 7 Please use a power meter accurately measure the true output R M S voltage of Inverter We use a power meter such as IDRC CP 350 or ABM 2019 to measure our product 2 5 AC Safety Groundin...

Страница 11: ...ING Do not operate the power inverter without connecting it to Ground Electrical shock hazard may result 2 6 Marking DC Wiring Connections Follow this procedure to connect the battery cables to the DC...

Страница 12: ...ates from an input voltage ranging from 20 to 32 VDC for 24V models 42 to 62VDC for 48V models 90 to 140VDC for 110V models 180 to 275VDC for 220V models The Inverter will indicate high and low DC vol...

Страница 13: ...cause its input voltage fell below 24V 48 110 220VDC Ref point 2 7 1 2 7 10 Over temp protection indicator OTP The over temp indicator indicates that the power inverter has shut itself down because it...

Страница 14: ...gy sources requirement Until output power is up to 300W the cooling fan will start to work in order to drop the inner temperature If the ventilation opening is obstructed the inverter will enter over...

Страница 15: ...on l Move the television as far away from the power inverter as possible l Keep the cables between the battery and the power inverter as short as possible and twist them together about 2 to 3 twists p...

Страница 16: ...al special or consequential even though caused by negligence or other fault 6 Important Safety Instructions WARNING Before you install and use your inverter be to read and save these safety instructio...

Страница 17: ...klaces and watches when working with a lead acid battery A lead acid battery produces a short circuit current high enough to weld a ring or the like to metal causing a severe burn 7 Appendices A 7 1 D...

Страница 18: ...N SPEC N is an integer number ranging from 0 to 9 The unit is Volt d O P voltage PPP P P is an integer number ranging form 0 to 9 The unit is Volt e O P current QQQ QQQ is a percent of maximum current...

Страница 19: ...y Low 5 SPEC 4 SPEC 3 SPEC 2 SPEC 1 SPEC 0 SPEC j Stop Byte cr Example Computer Q1 cr INVERTER 208 4 140 0 208 4 034 59 9 2 05 35 0 00110000 cr Means I P voltage is 208 4V SPEC I P fault voltage is 14...

Отзывы: