Room sensor
KWL-FTF eC
Installation and operating instructions
a measuring element for humidity and temperature measurement. Fine adjustment
by the user is possible.
Any use other than the intended use is prohibited!
1.8 Functionality
The calibratable room humidity and temperature sensor KWL-FTF eC measures
the relative humidity and ⁄ or temperature of air. It converts the measured variables
of humidity and temperature into a bus signal. In an elegant housing made of plastic,
with snap-on lid, base with 4-hole attachment for installation on vertically or hori-
zontally installed in-wall flush boxes, with predetermined breaking point for on-wall
cable entry. The relative humidity (in % r.H.) is the quotient of water vapour partial
pressure divided by the saturation vapour pressure at the respective gas tempera-
ture.
2.1 Technical data
KWL-FTF eC
Dimensions (W x H x D) mm
85 x 85 x 27 mm
Power supply
15...36 V DC
Load resistance
R
L
> 5 kΩ
Power consumption
0.3 W ⁄ 24 V DC;
Sensor
digital humidity sensor, with integrated tem-
perature sensor, small hysteresis, high
longterm stability
Measuring range humidity
0...100 % r.H.
Operating range humidity
0...95 % r.H. (non-precipitating air)
Deviation humidity
± 2,0 % (20...80 % r.H.) at +25°C,
otherwise ± 3,0 %
Output humidity
Bussignal
Measuring range temperature
0...+50°C
Operating range temperature
0...+50°C
Deviation temperature
± 0,2 K at +25°C
Output temperature
0 - 10 V
Ambient temperature
Storage –25...+50 °C; operation –5...+55 °C
Electrical connection
0.14 - 1.5 mm
2
, via screw terminals
Housing
plastic, material ABS, colour pure white (simi-
lar to RAL 9010)
Installation
wall mounting or on in-wall flusch box,
Ø 55 mm, base with 4-hole for mounting on
vertically or horizontally installed in-wall flush
boxes for cable entry from the back, with
predetermined breaking point for on-wall
cable entry from top ⁄ bottom in case of plain
on-wall installation
Long-term stability
± 1 % per year
Protection class
III (according to EN 60 730)
Protection type
IP 30 (according to EN 60 529)
Standards
CE conformity, according to EMC directive
2014 ⁄ 30 ⁄ EU, according to EN 61326-1,
according to EN 61326-2-3