Extension module
KWL-EM eC
for easyControls
Operating Instructions
7
5�3 Warm water post-heating
WW post-heating with WHSH HE 24V (0-10V)
5�3�1 Components required for installation
– Ventilation unit with easyControls 3.0 control system
– WHR 125 or WHR 160
– WHSH HE 24V (0-10V)
– 1 x KWL-EM eC
– 2 x KWL-LTK eC
5�3�2 Setup via web interface
1. Select the menu item Configuration on the web interface and Heating settings in the
submenu.
2. Select Auxiliary heating, Warm water post-heating.
The max� outdoor temperature setting defines the max� outdoor temperature up to
which the post-heating is active�
3. The desired supply air temperature can now be individually set on the homepage in
the ventilation profiles.
5�3�3 Setup via the KWL-BE Touch controller
1. Select the menu item Configuration and Heating settings in the submenu.
2. Select Auxiliary heating, Warm water post-heating.
The max� outdoor temperature setting defines the max� outdoor temperature up to
which the post-heating is active�
3. The desired supply air temperature can now be individually set on the homepage in
the ventilation profiles.
NOTE
NOTE
Содержание easyControls 3.0
Страница 13: ...Erweiterungsmodul KWL EM eC f r easyControls Montage und Betriebsvorschrift 11 DE...
Страница 25: ...EN Extension module KWL EM eC for easyControls Operating Instructions 11...
Страница 37: ...FR Module d extension KWL EM eC pour easyControls Notice de montage et d utilisation 11...
Страница 38: ...FR Module d extension KWL EM eC pour easyControls Notice de montage et d utilisation 12...
Страница 39: ...FR Module d extension KWL EM eC pour easyControls Notice de montage et d utilisation 13...