5. Enter the fan powers for supply and extract air according to the determined values for nominal ventilation under “Fan
6.3.3 Perform flow rate measurement for adjusting the system (fine adjustment)
• Measure the flow rates at all valves in the supply and extract air ducts.
• Add up the flow rates for the supply and extract air ducts.
• In case of deviations from the desired flow rates, adjust these accordingly by increasing or reducing.
• Adjust valves according to the design.
• Measure the flow rates at all valves in the supply and extract air ducts again to check the correct adjustment and
the total flow rate.