Air purifier AirPal 900/1200 U
Installation and Operating Instructions
EN
EN
11
5�2 Components
5�3 Filter
m
Danger to life due to electric shock!
An electric shock can result in death or serious injury.
The unit must be fully isolated from the mains power supply before all maintenance work and opening the terminal compart-
ment!
- Do not operate the unit without a proper electrical grounding/earthing.
- Make sure that the unit is connected to a power supply with a 30 mA individual RCD.
- Always disconnect the unit power supply before performing any service or maintenance work.
Make sure to use protective gloves and a protective mask (min� FFP2) before performing service and/or main-
tenance�
Filter information for AirPal 900/1200 U models, see the list below.
Filter name
Unit name
Filter class
Dimensions (LxWxH) (mm)
Order code
ELF-AirPal 1750+900/ePM10 70%
AirPal 900 U
ePM10 70%
457x610x100
40135-001
ELF-AirPal 1750+900/ePM1 80%
ePM1 80%
457x610x100
40136-001
ELF-AirPal 2200+1200/ePM10 70%
AirPal 1200 U
ePM10 70%
610x610x100
40138-001
ELF-AirPal 2200+1200/ePM1 80%
ePM1 80%
610x610x100
40139-001
1. Outlet
2. Silencer
3. Fan silencer
4. Fan
5. Power socket, status LEDs, Ope-
ration
6. Terminal box
7. UVC lamps
8. Silencer
9. Prefilter ePM1 80%
10. Prefilter ePM10 70%
11. Silencers