5
Central Ventilation Units KWL EC.. S Pro/WW
Installation and Operating Instructions
EN
KWL EC 2600 S Pro
Voltage/Frequency
3N 400 V~/50 Hz
Wiring diagram
SS-1370
Rated current – ventilation
2.3/2.3/2.3 A
Permissible air temperatures
-20 °C to 40 °C
Rated current – pre-heater
10.05/10.05/10.05 A
Weight
490 kg
Max. total rated current
12.35/12.35/12.35 A
Standby losses
<
1 W
Pre-heater (outlet)
6.9 kW
Design
IP20
Aux. heater (outlet) kW
--
Electrical supply line to UV
NYM-J
Air flow rates Vm
3
/h
840 - 1450 - 2065
KWL EC 2600 S Pro WW
Voltage/Frequency
3N 400 V~/50 Hz
Wiring diagram
SS-1370
Rated current – ventilation
2.3/2.3/2.3 A
Permissible air temperatures
-20 °C to 40 °C
Rated current – pre-heater
10.05/10.05/10.05 A
Weight
500 kg
Max. total rated current
12.35/12.35/12.35 A
Standby losses
<
1 W
Pre-heater (outlet)
6.9 kW
Design
IP20
Aux. heater (outlet) kW
9.3 (at 60/40 °C)
8.5 (at 50/40 °C)
5.3 (at 40/30 °C)
Electrical supply line to UV
NYM-J
Air flow rates Vm
3
/h
840 - 1450 - 2065