7.7 Diagrammes des fonctions régulateur de température
2.01
Refroidissement :
|
Valeur>Set = n+
|
:
|
ON
|
20 °C
Setpoint
05.05.2010
v_temp_cool_ctg.vsd
24 °C
Uout
[V]
5
10
Actual Value
[°C]
Min. Uout = 3.5 V
Max. Uout = 8.5 V
Min. Uout = 0.0 V
Max. Uout = 10.0 V
4 K
Pband
Chauffage :
|
Valeur>Set = n+
|
:
|
OFF
|
20 °C
Setpoint
4 K
Pband
05.05.2010
v_temp_heat_ctg.vsd
16 °C
Max. Uout = 10.0 V
Min. Uout = 0.0 V
Max. Uout = 8.5 V
Min. Uout = 3.5 V
Uout
[V]
Actual Value
[°C]
10
5
Débit minimum
10
Min. Uout = 3.5 V
Max. Uout = 10.0 V
20 °C
Setpoint
7 K
Pband
27 °C
25.04.2016
v_min_luft_abschalt_ctg.vsd
Uout
[V]
Actual Value
[°C]
5
H
MSCO = OFF
MSCO = -2.0 K
Prescription de montage et d
’
utilisation
ETR
Programmation
L-BAL-E293-F 1841 Index 001
Art.N
°
.
16/20