9.2.2 Settings for operation modes only
4.01
SETTING
SETTING
500 Pa
Setpoint 1
Setpoint 1
Setting range: Setpoint 1: 0...100 % sensor measuring range
Factory setting: 50 % sensor measuring range
500 Pa
Setpoint 2
Setpoint 2
Setting
“
Setpoint 2
”
e.g. reduced value for night operation.
Switching setpoint 1/2 via external voltage at terminals 1/2.
500 Pa
Pband
Pband
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range Pband: 0...100% sensor measuring range
Factory setting: 50 % sensor measuring range
0.0 V
Min. Uout
Min. Uout
Setting range minimal output voltage (basic speed):
0.0 V...10.0 V (setting takes priority over
“
Max. Uout
”
)
Factory setting: 0.0 V
10.0 V
Max. Uout
Max. Uout
Setting range maximal output voltage (speed limiter):
10.0 V...0.0 V
Factory setting: 10.0 V
10 Check sensor function
1. Program Mode
4.00
for pressure sensor.
2. Voltage supply (+Ub and GND) connected, output 0 - 10 V (A - GND) discon-
nected.
3. Remove pressure hoses and measure output signal, nominal = 0 V.
4. Create pressure at the "+" connection against the "-" connection (e.g. by
carefully
blowing in), measure the output signal (0...10 V measuring range).
5. If the sensor works, reconnect the pressure hoses and check these if necessary.
Installation and Operating Speci
fi
cation
EDR
Check sensor function
L-BAL-E192-GB 1320
Part.-No.
13/17